Isolation And Sound Emission - Trane R Series Installation Operation & Maintenance

Air-cooled helical-rotary liquid chiller 50 hz 400-1500 kw
Table of Contents

Advertisement

RLC-SVX02G-E4
Installation - Mechanical
Figure 4 – Rigging the Unit, Sizes 230-400
CAUTION
Refer to nameplate for unit weight
and additional installation
instructions contained inside the
control panel. Other lifting
arrangements may cause
equipment damage or serious
personal injury.
Isolation and Sound
Emission
The most effective form of isolation
is to locate the unit away from any
sound-sensitive area. Structurally-
transmitted sound can be reduced
by elastomeric vibration
eliminators. Spring isolators are not
recommended. Consult an
acoustical engineer in critical sound
applications.
RTAC
L
A
7133
3220
230 SE
7133
3220
240 SE
9138
3290
250 SE
9138
3290
250 HE
10056
3270
255 XE
9138
3290
275 SE
10975
3400
275 HE
10975
3400
275 XE
10056
3270
300 SE
11894
3430
300 HE
11894
3430
300 XE
10406
3280
350 SE
12244
3430
350 HE
12244
3430
355 XE
11325
3360
375 SE
13163
3380
375 HE
13163
3380
375 XE
12244
3430
400 SE
14082
3410
400 HE
14082
3410
400 XE
For maximum isolation effect,
isolate water lines and electrical
conduit. Wall sleeves and rubber-
isolated piping hangers can be used
to reduce the sound transmitted
through water piping. To reduce the
sound transmitted through electrical
conduit, use flexible electrical
conduit.
National and local codes on sound
emissions should always be
considered. Because the
environment in which a sound
source is located affects sound
pressure, unit placement must be
carefully evaluated. Sound-power
levels are available on request.
Container Pull out Hook
Maximum Shipping Weight
Aluminum
Copper
7652
8433
8031
-
7820
8640
8261
9157
9436
-
8581
9477
9623
10735
10168
-
9296
10300
10141
11365
10843
-
10617
11737
11924
13261
11713
-
11279
12507
12434
13883
13196
-
11881
13218
13109
14669
14029
-
21