Technical Data - Bosch RM2-DP12 Description

Table of Contents

Advertisement

9

Technical Data

Technical Data
Complies fully with the requirements of
Weight:
Dimensions (W x H x D):
Front panel: :
Storage temperature:
Operating temperature:
Slot:
Power Supply:
Current input:
Discharge capacity:
Internal supply for I/O modules:
Supply of bus interface (X71):
Degree of protection:
Class of protection:
Insulation test:
Atmospheric pressure:
Humidity rating:
Corrosion / chemical resistance:
Dirt resistance:
Transportability:
1070 072 449-102 (01.12) GB
RM2-DP12 Module
IEC1131-2
DIN VDE 0110
DIN EN 60204-1 (as per VDE 0113)
270 g approximately
30 x 182 x 115 mm
Module width 1
-25...+70°C as per IEC 1131-2
0...55°C
as per IEC 1131-2
The module must only be operated on slot 1 in the
mounting rack.
24 VDC (-15...+20%)
Power failures of up to 10 ms with nominal
voltage, with a 1 s break in between as per
IEC 1131-2.
1.35 A max.
24 V against protective earth:
0 V against protective earth:
7.5 V (+/- 5%) / 1.2 A max.
P5VISO/GNDISO (+/- 5%) / externally 100 mA
max. RS485, electrically isolated.
IP20 as per DIN VDE 0470-1
incorporated in the housing.
1 as per VDE 0106 T1 or VDE 0160 (IEC 536)
350 VAC
500 VDC
Operation up to 2000 m above sea level as per
IEC 1131-2
RH-2; 5%...95% as per IEC 1131-2.
F as per DIN 40040
Condensation not permissible.
The ambient air must be free of elevated concen-
trations of acids, alkali, corrosive agents, salt,
metal vapors or other electrically conductive
pollutants.
Degree of contamination 2 as per EN 1131-2
The RM2-DP12 module requires a dustfree
environment. The housing and compartments in
which the mounting rack is located must comply
with the minimum degree of protection IP54 as per
DIN VDE 0470-1.
Height of fall in packaging 1.0 m as per IEC 1131-2
Technical Data
9-1
4.7 nF
4.7 nF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents