Dp Diagnostic Information - Bosch RM2-DP12 Description

Table of Contents

Advertisement

8

DP Diagnostic Information

Byte
Bit 7
Bit 6
no.
0
1
6
7
x7
x6
x15
x14
8
9
x23
x22
x31
x30
10
11
x39
x38
x47
x46
12
1070 072 449-102 (01.12) GB
The RM2-DP12 module supports standard diagnostic information and the
extended diagnosis possibilities of the PROFIBUS-DP. Among the
extended diagnostic information, the RM2-DP12 supports the "identifier-
related diagnosis", i.e. that for each I/O module 1 bit is reserved in the
diagnostic buffer, which can indicate if the I/O module is under diagnosis
or not. The 'device- or channel-related diagnosis' provided in the
PROFIBUS standard is not supported by the RM2-DP12.
In case of a diagnosis, the diagnostic information will be made available
to the DP master module (master class 1) or to the programming device
(master class 2, e.g. for display on the DP monitor) via the PROFIBUS-
DP. In addition, status '1' will be displayed on the 7 segment display as a
group message for 'diagnosis is pending'.
Diagnostic information overview:
[Byte]
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7-12]
Coding of the identifier-related diagnosis:
Bit 5
Bit 4
Bit 3
0
0
0
x5
x4
x3
x13
x12
x11
x21
x20
x19
x29
x28
x27
x37
x36
x35
x45
x44
x43
Identifier-related diagnosis:
A set bit means that in this I/O range a diagnosis is pending.
DP Diagnostic Information
Function
Station_Status_1
Station_Status_2
Station_Status_3
Master_Add
Ident_High
Ident_Low
Header for external diagnosis
6 bytes external diagnosis
Bit 2
Bit 1
Bit 0
1
1
1
x2
x1
x0
x10
x9
x8
x18
x17
x16
x26
x25
x24
x34
x33
x32
x42
x41
x40
Significance
Header byte
Module no.: 0-7
Module no.: 8-15
Module no.: 16-23
Module no.: 24-31
Module no.: 32-39
Module no.: 40-47
8-1