4.3.3 PRESET MULTIPLE REGS (0X10)
With this telegram the master can change one or more registers, whereby the
registers must lie in series.
Example:
The registers 24 (+25) + 384 (Pmax Thyro-A h RLP1/Thyro-AX h RLP2, Control-
ler 3) are to be changed to 10kW in the bus module with the address 100.
(24+3*128=408, 408-(1 x 256) = 152; 10000 = 39,16 (256 * 39 + 16 = 10000)
Inquiry:
ADDRESS
fUnC-
TIOn
100
16
Response:
ADDRESS
fUnCTIOn
100
16
Error:
Should the register's address lie outside the address location, the
Exception Response „ILLEGAL DATA ADDRESS" is transmitted (see-
Chapt. 4.3.5).
Response:
ADDRESS
fUnCTIOn
100
144
Should there be registers which can only be read out, the change
requested is ignored.

4.3.4 REPORT SLAVE ID (0X11)

With this telegram the master can read out the slave ID.
Example:
The ID is to be read out from the bus module with the address 100.
Inquiry:
ADDRESS
100
REGISTER
nUMBER
1, 152
0, 2
REGISTER
1, 152
ERROR CODE
2
fUnCTIOn
17
nO.
DATA
ByTES
4
0, 0, 39, 16
nUMBER
CRC
0, 2
200, 46
CRC
221, 222
CRC
235, 124
CRC
3, 4