Communications Between Fault-Tolerant Systems And Pcs - Siemens SIMATIC S7-400H Manual

Automation system, fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Communication Functions
8.4.3

Communications between Fault-Tolerant Systems and PCs

Availability
When fault-tolerant systems are connected to a PC, the availability of the overall
system concentrates not only on the PCs (OS) and their data management but
also on data acquisition on the programmable logic controllers.
PCs are not fault-tolerant on account of their hardware and software
characteristics. They can be arranged in a redundant manner in a system,
however. The availability of this kind of PC (OS) system and its data management
is ensured by means of suitable software such as WinCC Redundancy.
Communications take place via fault-tolerant connections.
The "S7-REDCONNECT" software package as of V1.3 is a requirement for
fault-tolerant communication on a PC. It makes it possible to connect a PC to an
optical network with a CP or to a redundant bus system with two CPs.
Configuring connections
No additional configuration of fault-tolerant communications is required at the PC
end. Connection configuration is taken care of by the STEP 7 project in the form of
an XDB file at the PC end.
You can find out how to use STEP 7 fault-tolerant S7 communications to integrate
a PC in your OS system in the WinCC documentation.
Redundancy
block diagram
Figure 8-7
8-14
Fault-tolerant system a
CPU
CP
a1
a1
OLM
OLM
Fault-tolerant
system a
CPUa1
CPa1
CPUa2
CPa2
2oo2 redundancy
Example of redundancy with fault-tolerant system and redundant bus system
PC
CP
WinCC
server
1
OLM
Bus 1
CP 1
PC
Bus 2
Automation System S7-400H Fault-tolerant Systems
System bus as opti-
cal two-fiber ring
A5E00068197-07