Failure And Replacement Of An Im 460 And Im 461 Interface Module - Siemens SIMATIC S7-400H Manual

Automation system, fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

10.1.6
Failure and Replacement of an IM 460 and IM 461 Interface
Module
The IM 460 and IM 461 interface modules make it possible to connect expansion
racks.
Initial situation
The S7-400H is in redundant system mode
and one interface module fails.
Procedure
To change an interface module, perform the following steps:
Step
1
2
3
4
5
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07
Failure and Replacement of Components During Operation
Failure
What Has To Be Done?
Turn off the power supply of the central
rack.
Turn off the power supply of the
expansion unit in which you want to
replace the interface module.
Extract the interface module.
Insert the new interface module and
turn the power supply of the expansion
unit back on.
Switch the power supply of the central
rack back on and start the CPU.
How Does the System React?
Connected expansion unit is turned off.
Both CPUs report the event in the
diagnostics buffer and via OB 86.
How Does the System React?
The partner CPU switches to
single mode.
-
-
-
CPU performs automatic LINK-UP
and UPDATE.
CPU changes to RUN and
operates as the standby CPU.
10-11