Effects Of Link-Up And Update; Properties Of Link-Up And Update - Siemens SIMATIC S7-400H Manual

Automation system, fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Linking and Synchronizing
6.1

Effects of Link-up and Update

Link-up and update are indicated by the REDF LEDs on the two CPUs. On link-up
these LEDs flash with a frequency of 0.5 Hz, and on update with a frequency of
2 Hz.
Link-up and update have various effects on the execution of the user program and
the communication functions.
Table 6-1
Process
Execution of the user
program
Deletion, loading,
generation and
compression of blocks
Execution of
communication
functions, PG operation
CPU self-test
Test and commissioning
functions, such as
"Monitor and Control
Tag", "Monitor (On/Off)"
Processing of the
connections to the
master CPU
Processing of the
connections to the
standby CPU
6-2

Properties of link-up and update

Linking
All priority classes (OBs)
are executed.
Blocks cannot be deleted,
loaded, generated or
compressed.
If these actions are being
executed, link-up and
update will not be possible.
Communication functions
are being executed.
Will not be performed
No test and commissioning
functions are possible.
If these actions are being
executed, link-up and
update will not be possible.
All the connections remain;
no new connections can be
made.
All the connections are
broken; no new
connections can be made.
Update
Execution of the priority classes
is delayed by sections. All the
requirements are caught up with
after the update.
You will find the details in the
sections which follow.
Blocks cannot be deleted,
loaded, generated or
compressed.
Execution of the functions is
restricted and delayed by
sections. All the delayed
functions are caught up with after
the update.
You will find the details in the
chapters which follow.
Will not be performed
No test and commissioning
functions are possible.
All the connections remain; no
new connections can be made.
Broken connections will only be
re-made after the update
All the connections are already
broken. They are aborted on
link-up.
Automation System S7-400H Fault-tolerant Systems