Electrical installation

What this chapter contains

This chapter contains a reference to the connection diagram and a list of items to
consider in the electrical installation.

Connection diagram

See

Considerations

Follow the cabling recommendations of the drive Hardware Manual.
Leave at least 0.5 m space between the unit and the power cables and drive
module. If 0.5 m is impossible, install as far as possible.
Use shielded twisted-pair cables between the transformers and the RSYC unit.
Ground the shields with as short pigtails as possible. Cut and insulate any unused
conductors at both ends of the cables. See Connection diagram.
Use shielded twisted-pair cables between the RSYC unit and the drive. Ground the
shields at the drive module end according to the instructions given in the drive
Hardware Manual.
Use shielded twisted-pair cables between the unit and the contactor control
circuitry. Ground the shields with as short pigtails as possible.
Dimension selects the cable in between the main circuit and the synchronizing
transformers according to the main circuit voltage. Protect the cable with fuses if
necessary.
Connection diagram
on page
11.
15
Electrical installation