EN – R6…R9 Quick installation guide 21 EN – R6…R9 Quick installation guide This guide briefly describes how to install the drive. For complete information on installation, see ACH580-01 (0.75 to 250 kW) hardware manual (3AUA0000076331 [English]). For start-up instructions, see chapter EN –...
22 EN – R6…R9 Quick installation guide For information on reforming the capacitors, see Converter module capacitor reforming instructions (3BFE64059629 [English]), available on the Internet at www.abb.com/drives/documents. Select the power cables Size the power cables according to local regulations to carry the nominal current given on the type designation label of your drive.
EN – R6…R9 Quick installation guide 23 Check the insulation of the power cables and the motor Check the insulation of the input cable according to local regulations before connecting it to the drive. See figure on page 1. Check the insulation of the motor cable and motor before connecting it to the drive.
Page 24
24 EN – R6…R9 Quick installation guide WARNING! Do not install the drive with the ground-to-phase varistor connected on an IT system (an ungrounded power system or a high-resistance-grounded [over 30 ohms] power system), otherwise the varistor circuit can be damaged.
EN – R6…R9 Quick installation guide 25 Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see steps 5, IP21 and 5, IP55 in figure R6…R9 Figures A...
26 EN – R6…R9 Quick installation guide Connect the power cables See figure on page 39. Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE conductor for drive or motor, make sure that is has sufficient conductivity for the PE.
EN – R6…R9 Quick installation guide 27 Connect the control cables See figure on page 40. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the default configuration in use. The default connections of the HVAC default configuration are shown in section Default I/O connections on page 28.
28 EN – R6…R9 Quick installation guide Default I/O connections Default I/O connections of the HVAC default configuration are shown below. Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND...
EN – R6…R9 Quick installation guide 29 Install optional modules, if any See chapter Electrical installation in ACH580-01 (0.75 to 250 kW) hardware manual (3AUA0000076331 [English]). Install side plates and covers See figure R6…R9 Figures E on page 41. IP21 1.
HVAC control panel. For complete information on start-up, see ACH580 firmware manual (3AXD50000027537 [English]). Before you start Ensure that the drive has been installed as described in chapter EN – R6…R9 Quick installation guide on page (frames R6…R9). Start-up with the First start assistant on an HVAC control...
Page 32
Refer to the motor nameplate for the following nominal value settings of the motor. Enter the values exactly as shown on the motor nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl.
Page 33
EN – Quick start-up guide 33 To change a value in an edit view: • Use to move the cursor left and right. • Use to change the value. Press (Save) to accept the new setting, or press (Cancel) to go back to the previous view without making changes.
Page 34
34 EN – Quick start-up guide Change the units shown on the panel if needed. • Go to the edit view of a selected row by pressing • Scroll the view with Go to the next view by pressing (Next). To select a value in an edit view: •...
Page 35
EN – Quick start-up guide 35 The Home view monitoring the values of the selected signals is shown on the panel.
Page 36
36 EN – Quick start-up guide 2 – Hand/Off/Auto operation The drive can be in remote control or local control, and in local control there are additionally two different modes. Remote control: Drive is controlled from the I/O or the fieldbus. •...
Page 37
Compliance with the European Machinery Directive 2006/42/EC Declaration of conformity...
Page 39
R6…R9 Figures A IP21 IP21 ONLY IT AND CORNER-GROUNDED TN SYSTEMS M6×12 571/ 623/ 701/ 718/ (mm/in) 22.5 24.5 27.6 28.3 531/ 583/ 658/ 658/ (mm/in) 20.9 22.9 25.9 25.9 213/ 245/ 263/ 345/ (mm/in) 10.4 13.6 300/ 300/ 300/ 300/ d >...