Select analogue input AI1 for actual
signal for PID controller.
Set minimum value for ACT1.
Set maximum value for ACT1.
Deactivate integration term of PID
controller.
Activate Trim function and define
trimming relative to maximum speed.
Select parameter 40.16 for the source
of the trim reference.
Set trim reference to 50%.
Define the maximum effect of trim (that
is added to the drive reference)
Macro selection and motor control mode
Select factory macro.
Select motor control mode.
Define the motor parameters.

Checking the operation of the RSYC unit

WARNING! Read and follow the instructions in the drive Hardware Manual. Ignoring
the instructions can cause physical injury or death, or damage to the equipment.
Ensure that the drive is disconnected from the supply line and all other precautions
described in the safety instructions have been taken into consideration.
Before starting, ensure that the contactor control circuit connection at terminal J2 of
the RSYC unit is disconnected.
For the use of control panel, see ACS800 Standard Control Program 7.x Firmware
Manual (3AFE64527592 [English]).
Start-up
Parameter value
Additional information
40.07 = AI1
BUF OUT signal from RSYC unit, 0 ... 10 V.
Below 5 V = supply line frequency exceeds drive
output frequency.
5 V = Supply line frequency and drive output
frequency are equal and phases match.
Above 5 V = supply line frequency is lower than
drive output frequency
40.09 = 0.00%
-
40.10 = 100.00%
-
40.13 = OFF
-
40.14 = DIRECT
PID controller output is relative to maximum
speed limit (Par. 20.02).
40.15 = PAR
40.16
40.16 = 50.00%
Trim reference is equal to actual signal when the
synchronization conditions are valid i.e. when
AI1= 5 V. See parameter 40.07 above.
40.17 = 1.00%
-
99.02 =
Other macros except PID CNTRL are also
FACTORY
possible (PID cannot be used as the PID
controller is reserved for Trim function).
99.04 = DTC
-
99.05 ...99.10
See ACS800 Standard Control Program 7.x
Firmware Manual (3AFE64527592 [English]).