Omron EQUO Series User Manual page 60

Differential pressure station; thermo-humidity station; air thermo logger
Hide thumbs Also See for EQUO Series:
Table of Contents

Advertisement

(3) Upper limit of the temperature threshold value (DEGHI)
Sets the upper limit of the temperature threshold value for an alarm output.
When the measured temperature is higher than the set value, "ALM" and the alarm output are
turned ON.
Setting range (numeric value input type):
-20.0 °C to 60.0 °C
Initial value:
60.0 °C
(4) Lower limit of the temperature threshold value (DEGLO)
Sets the lower limit of the temperature threshold value for an alarm output.
When the measured temperature is lower than the set value, "ALM" and the alarm output are
turned ON.
Setting range (numeric value input type):
-20.0 °C to 60.0 °C
Initial value:
-20.0 °C
(5) Upper limit of the humidity threshold value (RH HI)
Sets the upper limit of the humidity threshold value for an alarm output.
When the measured humidity is higher than the set value, "ALM" and the alarm output are
turned ON.
Setting range (numeric value input type):
0.0 % to 100.0 %
Initial value:
100.0 %
(6) Lower limit of the humidity threshold value (RH LO)
Sets the lower limit of the humidity threshold value for an alarm output.
When the measured humidity is lower than the set value, "ALM" and the alarm output are
turned ON.
Setting range (numeric value input type):
0.0 % to 100.0 %
Initial value:
0.0 %
(7) Setting alarm hold
Set whether or not for the alarm output ON state and "ALM" ON state on the display to be
maintained when the measured value is returned to within the range of upper/lower limit of the
threshold value from outside of the range (alarm state) during measurement in RUN mode.
To release the alarm from the maintained state, hold the MODE key (at least 3 seconds) for
"ALM" to turn off, then the alarm output stops.