Ssr2 System Status Register (2) Protection Relay's Mode And State; Ssr3 System Status Register (3) Data Available 1 (Client-Dependent) - ABB RET615 Manual

Transformer protection and control
Hide thumbs Also See for RET615:
Table of Contents

Advertisement

1MRS756878 H
2.4.1.18
Table 121:

SSR2 System status register (2) protection relay's mode and state

RegA
Type
Scale
129.00
Bit
129.01
Bit
129.02
Bit
129.03
Bit
129.04
Bit
129.05
Bit
129.06
Bit
129.07
Bit
129.08
Bit
129.09
Bit
129.10
Bit
129.11
Bit
129.12
Bit
129.13
Bit
129.14
Bit
129.15
Bit
2.4.1.19
Table 122:

SSR3 System status register (3) data available 1 (client-dependent)

RegA
Type
Scale
130.00
Bit
130.01
Bit
130.02
Bit
130.03
Bit
130.04
Bit
130.05
Bit
130.06
Bit
130.07
Bit
130.08
Bit
130.09
Bit
130.10
Bit
130.11
Bit
130.12
Bit
Table continues on next page
RET615
Point List Manual
SSR2 System status register (2) protection relay's mode and state
IEC 61850 name
SSR3 System status register (3) data available 1 (client-dependent)
IEC 61850 name
SA name
Description
Device test mode
< reserved >
Remote/Local state
Active setting group
- bit 0
- bit 1
- bit 2
Protection relay's timesynch
failure
< reserved >
Last reset cause a
Last reset cause b
Last reset cause c
< reserved >
< reserved >
< reserved >
< reserved >
< reserved >
SA name
Description
Unread event records available
Unread fault records available
< reserved >
< reserved >
Any momentary bit updated
Any mcd bit set
Device restart bit
< reserved >
Event record selected
Fault record selected
< reserved >
< reserved >
< reserved >
Section 2
Modbus data mappings
Values
1=Test mode
0
0/1=Rem/Loc
SG=1...6
1=Failure
0
1=Cold start
1=Watchdog
1=Warm start
0
0
0
0
0
Values
1=Available
1=Available
0
0
1=Updated
1=Set
1=IED restart
0
1=Selected
1=Selected
0
0
0
67