Ld0.Rescmmxu2 Residual Current Measurement (2); Ld0.Resvmmxu1 Residual Voltage Measurement (1); Ld0.Rovptov1 Residual Overvoltage Protection (1); Ld0.Rovptov2 Residual Overvoltage Protection (2) - ABB RET615 Manual

Transformer protection and control
Hide thumbs Also See for RET615:
Table of Contents

Advertisement

1MRS756878 H
2.3.1.53
Table 56:

LD0.RESCMMXU2 Residual current measurement (2)

BitA
RegA
2764
172.12
2765
172.13
2766
172.14
2767
172.15
2.3.1.54
Table 57:

LD0.RESVMMXU1 Residual voltage measurement (1)

BitA
RegA
3048
190.08
3049
190.09
3050
190.10
3051
190.11
2.3.1.55
Table 58:

LD0.ROVPTOV1 Residual overvoltage protection (1)

BitA
RegA
3168
198.00
3169
198.01
3170
198.02
3171
198.03
2.3.1.56
Table 59:

LD0.ROVPTOV2 Residual overvoltage protection (2)

BitA
RegA
3172
198.04
3173
198.05
3174
198.06
3175
198.07
RET615
Point List Manual
LD0.RESCMMXU2 Residual current measurement (2)
IEC 61850 name
SA name
LD0.RESCMMXU2
.HiAlm.stVal
HIGH_ALARM
.mcd
.HiWrn.stVal
HIGH_WARN
.mcd
LD0.RESVMMXU1 Residual voltage measurement (1)
IEC 61850 name
SA name
LD0.RESVMMXU1
.HiAlm.stVal
HIGH_ALARM
.mcd
.HiWrn.stVal
HIGH_WARN
.mcd
LD0.ROVPTOV1 Residual overvoltage protection (1)
IEC 61850 name
SA name
LD0.ROVPTOV1
.Str.general
START
.mcd
.Op.general
OPERATE
.mcd
LD0.ROVPTOV2 Residual overvoltage protection (2)
IEC 61850 name
SA name
LD0.ROVPTOV2
.Str.general
START
.mcd
.Op.general
OPERATE
.mcd
Modbus data mappings
Description
High alarm
High warning
Description
High alarm
High warning
Description
General start
General operate
Description
General start
General operate
Section 2
Values
1=Alarm
1=Warning
Values
1=Alarm
1=Warning
Values
1=Start
1=Operate
Values
1=Start
1=Operate
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents