Supported Information Types; Function Status Fault Protection For Iec 60870-5-103; I103Fltprot; Functionality - ABB Relion 630 Series Communication Protocol Manual

Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 4
IEC 60870-5-103 vendor specific implementation
4.1.4.5
4.1.5
4.1.5.1
24

Supported information types

Earth fault indications in monitor direction, I103EF
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 14:
I103EF supported indications
Info. no.
Message
48
Earth fault L1
49
Earth fault L2
50
Earth fault L3
51
Earth fault forward
52
Earth fault reverse

Function status fault protection for IEC 60870-5-103

I103FLTPROT

Functionality

I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to
a correspondent signal present in the configuration. For example: 68_TRGEN
represents the General Trip of the device, and therefore must be connected to the
general trip signal SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that
is triggering the Disturbance Recorder and the respective configured signal to the
IEC 60870-5-103 I103FLTPROT.
Supported
No
No
No
Yes
Yes
Communication Protocol Manual
1MRS757203 A