Power Connections - Lutron Electronics LL-INTMOUNT Integration Manual

Pir sensor
Table of Contents

Advertisement

Available languages

Available languages

Electrical Integration (continued)

Power Connections

The LL-INTMOUNT can accept an input voltage range of 120 – 277 V~ (phase-to-phase possible).
The LL-INTMOUNT switches to the load the same voltage it is fed.
The Load output connection can support an electronic ballast load of up to 1000 W at 277 V~ and 600 W at
120 V~. Multiple loads can be driven by the same LL-INTMOUNT as long as the total wattage does not exceed
the maximum wattage for the given drive voltage.
OEM Validation Process
In order to ensure proper Lutron by Limelight system functions, all lighting fixtures that plan to integrate
LL-INTMOUNT into them need to be validated through Lutron. A picture or fixture design plan with the intended
install location called out should be provided to Lutron via LimelightOEMintegration@lutron.com. Lutron may
request additional fixture information along with a sample fixture for further RF testing. If a sample is requested,
the required performance testing may take up to 3 weeks, starting from when the sample is received by Lutron.
For best RF performance of the LL-INTMOUNT, the antenna should be kept 1.25 in (31.75 mm) from other metal
components and should not be concealed in a metal box. If either of these are violated a sample fixture
will be requested.
Dimming Connections
The LL-INTMOUNT outputs an analog 0.5 – 10 V- for dimming (0 – 10 V- dimming output, capable of sinking
up to 1.0 mA of 0 – 10 V- signal). The sum of the dimming input sink current for all drivers connected to the
LL-INTMOUNT should not exceed this requirement.
The dimming connection is separated from all other external connections (neutral, hot, load, external sensor
connector) with 100k ohms of resistance. This circuit is still an electric shock hazard and should not be
accessible in the end product.
Strain Relief
It is strongly recommended to zip tie the 5 wires, coming from the 5-pin connector, together within 2 in (51 mm)
of the connector to provide strain relief as shown below.
Limelight by Lutron OEM Integration Guide
Antenna location. Keep
metal components 1.25 in
(31.75 mm) away when
possible.