Lutron Electronics LL-INTMOUNT Integration Manual page 2

Pir sensor
Table of Contents

Advertisement

Available languages

Available languages

Electrical Integration
Warning: Shock Hazard! May result in serious injury or death. Disconnect power before servicing or
installing. This is a line voltage product and should only be installed / assembled into a fixture when power
is not applied.
5-Pin Connector (J1)
The LL-INTMOUNT has a 5-pin connector for connection to the AC power and the luminaire. During
manufacturing, solid core or tinned wires can be pressed into the connector slots. For stranded wires, press
down on the button next to each connector slot to allow wire entry. Releasing the button will cause the
connector to grip the wire.
Wire Gauge: 16 – 20 AWG (1.5 – 0.5 mm
16 – 20 AWG (1.5 – 0.5 mm
Wire Strip Length: 0.3 – 0.35 in (8 – 9 mm). Wires should be stripped 0.3 – 0.35 in (8 – 9 mm) for optimal fit into the
5-pin connector.
The 5 pins are called out in the image below.
Typical Wiring Diagram
LED Driver
Limelight by Lutron OEM Integration Guide
2
). The 5-pin connector can accept wire gauges in the range of
2
).
Luminarie Power
Connection
Line/
Hot
Neutral
Switched Hot
DIM+
DIM-
Note: All wire retentions meet or exceed UL1059 and UL486
requirements
Line (black)
Neutral (white)
Switched Hot (red)
DIM+ (violet)
DIM- (grey)
LL-INTMOUNT
2
LL-PIR
Continued on next page...