Commissioning
4.5 Connect MASTERDRIVES MC to the Technology-CPU
Procedure
The following section describes the procedure to run the script file "STDTLG5_T4_V21.ssc":
● With Drive Monitor / Drive ES click on the field Execute script file... under the menu item
Note
The 6SE70MC converter/inverter may not be in the "Run" state (r001=14).
The possible settings for the sources of the digital outputs for "Parameter > Controlled
start-up > Basic functions" are reset at the next "Execute script file..."!
● You are now guided ONLINE via WINDOWS windows. The script file should first be
Figure 4-49
● After the start you must accept the liability exclusion clause and acknowledge the
Note
You can stop the execution of the script file at any time using the Cancel button.
● Carefully read the contents of the message box with the setting information for the
Figure 4-50
Message box with setting information for P340
78
File, select the script file "STDTLG5_T4_V21.ssc" for standard telegram 5 and open this.
started:
Starting the script file "STDTLG5_T4_V21.ssc"
connection of the Motion Control to the Technology CPU for standard telegram 5.
application-dependent parameter P340 (pulse frequency) and acknowledge the message.
Connecting SIMOVERT MASTERDRIVES MC to the Technology-CPU
Product Information, 03/2008, A5E00272072-05