Carrier 19XRV Series Start-Up And Service Instructions

With pic iii/pic 6 controls rockwell powerflex 755 vfd option

Advertisement

Quick Links

Start-Up and Service Instructions

SAFETY CONSIDERATIONS

Centrifugal and screw compressor liquid chillers are designed to
provide safe and reliable service when operated within design
specifications. When operating this equipment, use good judg-
ment and safety precautions to avoid damage to equipment and
property or injury to personnel.
Be sure you understand and follow the procedures and safety pre-
cautions contained in the chiller instructions as well as those listed
in this guide.
Failure to follow these procedures will result in severe personal
injury or death.
ONLY QUALIFIED electrical personnel familiar with the
construction and operation of this equipment and the hazards
involved should install, adjust, operate, or service this equip-
ment.
READ AND UNDERSTAND this manual and other applica-
ble manuals in their entirety before proceeding. Failure to ob-
serve this precaution could result in severe bodily injury or loss
of life.
DO NOT install modification kits with power applied to the
drive. Disconnect and lock out incoming power before at-
tempting such installation or removal. Failure to observe this
precaution could result in severe bodily injury or loss of life.
UNUSED WIRES in conduit must be grounded at both ends to
avoid a possible shock hazard caused by induced voltages. Al-
so, if a drive sharing a conduit is being serviced or installed, all
drives using this conduit should be disabled to eliminate the
possible shock hazard from cross-coupled motor leads. Failure
to observe these precautions could result in bodily injury.
DO NOT VENT refrigerant relief valves within a building.
Outlet from rupture disc or relief valve must be vented out-
doors in accordance with the latest edition of ANSI/
ASHRAE 15 (American National Standards Institute/Ameri-
can Society of Heating, Refrigerating, and Air-Conditioning
Engineers). The accumulation of refrigerant in an enclosed
space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/
ASHRAE 15, especially for enclosed and low overhead spac-
es. Inhalation of high concentrations of vapor is harmful and
may cause heart irregularities, unconsciousness, or death. Mis-
use can be fatal. Vapor is heavier than air and reduces the
amount of oxygen available for breathing. Product causes eye
and skin irritation. Decomposition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a
chiller for any purpose. Oxygen gas reacts violently with oil,
grease, and other common substances.
(Dangers continued in next column.)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190061-01
DANGER
Printed in U.S.A.
with PIC III/PIC 6 Controls
Rockwell PowerFlex 755 VFD Option
NEVER EXCEED specified test pressures. VERIFY the al-
lowable test pressure by checking the instruction literature and
the design pressures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed
and functioning before operating any chiller.
THERE IS A RISK OF INJURY OR DEATH by electrocu-
tion. High voltage may be present on the motor leads even
though the motor is not running. Open the power supply dis-
connect before touching motor leads or terminals.
Failure to follow these procedures may result in personal inju-
ry or death.
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles
and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from system
using both high-pressure and low-pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in
contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter and
remove component from unit. Use a pan to catch any oil
that may come out of the lines and as a gage for how
much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
DO NOT work on high-voltage equipment unless you are a
qualified electrician.
DO NOT WORK ON electrical components, including control
panels, switches, VFD, or oil heater until you are sure ALL
POWER IS OFF and no residual voltage can leak from capaci-
tors or solid-state components.
LOCK OPEN AND TAG electrical circuits during servicing.
IF WORK IS INTERRUPTED, confirm that all circuits are
de-energized before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into
the eyes. USE SAFETY GOGGLES. Wash any spills from
the skin with soap and water. If liquid refrigerant enters the
eyes, IMMEDIATELY FLUSH EYES with water and con-
sult a physician.
(Warnings continued on next page.)
Form 19/23-8SS
Pg 1
19XRV, 23XRV
DANGER
WARNING
6-19
Replaces: 19/23-7SS

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 19XRV Series

  • Page 1: Safety Considerations

    19XRV, 23XRV with PIC III/PIC 6 Controls Rockwell PowerFlex 755 VFD Option Start-Up and Service Instructions SAFETY CONSIDERATIONS DANGER Centrifugal and screw compressor liquid chillers are designed to NEVER EXCEED specified test pressures. VERIFY the al- provide safe and reliable service when operated within design lowable test pressure by checking the instruction literature and specifications.
  • Page 2: Table Of Contents

    INTRODUCTION DO NOT climb over a chiller. Use platform, catwalk, or stag- The Carrier VFD option Start-Up and Service Manual is intended ing. Follow safe practices when using ladders. for trained and qualified service personnel and is to be used during USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift...
  • Page 3: Abbreviations And Explanations

    — Variable Frequency Drive Required Publications WARNING The Carrier VFD option Start-Up and Service Manual must be Before removing the drive enclosure, open access door and used with the following manuals: verify that the DC bus voltage has dropped to zero by checking •...
  • Page 4: Components And Physical Data

    0477 – 477 a19-2381 * For Carrier applications, maximum continuous amp ratings are 230, 269, 335, and 445. † For 600 v applications, CB1 = 65 KAIC and CB2 = 42 KAIC rating (575 v). Fig. 5 — Rockwell Automation Drive Assembly Catalog Number Nomenclature: 23XRV Units...
  • Page 5 LEGEND NAME DESCRIPTION Power Terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3 PE Grounding Studs Terminating point to chassis ground for incoming motor shield DC Bus and Brake +DC, -DC, BR1, BR2 Terminals PE-A and PE-B MOV and CMC Jumper Wires DC+ and DC- Bus Voltage Test Points Fig.
  • Page 6 a19-2379 36.00 REF 22.00 40.00 SIDE VIEW FRONT VIEW NOTE: Dimensions shown in inches. Fig. 8 — 19XRV Enclosure Dimensions — Frames 6 and 7 a19-2011 NOTE: Dimensions shown in inches. Fig. 9 — 23XRV Enclosure Dimensions — Frame 7...
  • Page 7: Start-Up

    CAUTION From the HMI control panel screen: If other than refrigerant cooling is used, before connecting the a. Carrier Part Number and Revision drive to the incoming power, make sure that the coolant is cir- b. Software Number culating and has no leaks.
  • Page 8: Configure The Vfd

    VFD_CONF screen. Table 3 shows parameters in the Unit Mounted VFD Configuration menu for PIC6. Parameters in ital- ics are to be entered or confirmed at start-up. Parameters in bold are to be changed only after consulting with Carrier service engi- neering. Table 2 — VFD Configurations (PIC3/VFD_CONF)
  • Page 9: Commissioning The Unit

    Imbalance Calculation Formula Commissioning the Unit The commission procedure is as follows: (VAB + VBC + VCA) Vavg If the chiller has been stored outdoors, allow at least 24 hours room temperature stabilization prior to commis- (Vmax – Vmin) x 100 sioning.
  • Page 10: Service

    Alert and Alarm codes. These codes signal a problem detected CONNECTED DISCONNECTED during self-tuning or drive operation. Note the following differ- ences between Carrier and Allen-Bradley terminology: COMMON MODE • A warning message on the HMI is an ALERT. •...
  • Page 11: Verifying That Dc Bus Capacitors Are

    Table 4 — Drive Status Indicator Descriptions NAME COLOR STATE DESCRIPTION Green Flashing Drive ready but not running, and no faults are present. Steady Drive running, no faults are present. Yellow Flashing Drive is not running. A type 2 (non-configurable) alarm condition exists, and the drive cannot be started.
  • Page 12 (PIC6) screen. Verify phase-to-phase and phase-to-ground line Undervoltage Low DC bus voltage voltage. VFD Circuit Board malfunction. Contact Carrier Service. Verify phase to phase and phase to ground line 205 (166) Overvoltage High DC bus voltage voltage. Monitor AC line for high transient volt- age conditions.
  • Page 13 Table 5 — Powerflex 755 Fault Code Descriptions and Corrective Actions (cont) FAULT ICVC PIC6 CODE FAULT FAULT FAULT TYPE DESCRIPTION CORRECTIVE ACTION ON VFD STATE STATE HIST SCREEN To reset the processor, cycle power to chiller, check VFD_CONF settings and save settings If this fault appears, there may be a prob- Load Loss when exiting VFD_CONF (PIC3)/CFGUMVFD...
  • Page 14: With Input Power Off

    Table 5 — Powerflex 755 Fault Code Descriptions and Corrective Actions (cont) FAULT ICVC PIC6 CODE FAULT FAULT FAULT TYPE DESCRIPTION CORRECTIVE ACTION ON VFD STATE STATE HIST SCREEN Autn Enc Angle P78 [Encdrlss AngComp] is out of range. See VFD Fault Code 15 Autn Spd Rstrct See VFD Fault Code 15 See VFD Fault Code 15...
  • Page 15: Servicing The Drive

    Check to be sure that the voltage between DC+ and DC- Table 6 — Diode Checks and from each DC terminal to the chassis is zero before METER LEAD METER READING proceeding. See Fig. 20. Remove the enclosure. See Fig. 21. 0.5 v Infinite (OL) REMOVING THE DRIVE...
  • Page 16: Rigging The Enclosure

    When replacing the drive, reverse the procedures and tighten to RIGGING THE ENCLOSURE the torques for Frames 6 and 7 power terminal block listed in Ta- Where overhead room and/or clearance in front of the drive en- ble 7. closure is insufficient to allow the drive to be safely removed from the enclosure, the entire enclosure may have to be removed from Table 7 —...
  • Page 17: Replacing The Gateway

    REPLACING GATEWAY (A-B20-750-20COMM ENCLOSURE TOP PIC3 / 20-COMM-H (PIC6) OPTION CARD) FRONT CORNER OF IS REMOVABLE DRIVE COMPARTMENT IS REMOVABLE Follow these steps for removing and replacing the existing gate- way: DRIVE POSITIONED FOR VERTICAL LIFT Disconnect power to the drive. Before removing the enclo- sure, open the access door on the front of the drive.
  • Page 18: Chill Plate Fan And Internal Fan Replace- Ment

    MOUNTING PLATE GATEWAY 2.6 N•m (23 lb•in.) INTERNAL FAN A19-1840 2.6 N•m (23 lb•in.) Fig. 29 — Internal Fan, Frame 6 A19-1820 Frame 7 (chill plate fan kit Z1P-FAN-A7-A): Disconnect power to the drive. Before removing the enclo- Fig. 27 — Mount COMM Card Plate to Drive sure, open the access door on the front of the drive.
  • Page 19 C R 1 LINE- C R 6 T B 4 CABLE ACCESS DIST. CUTOUT SIDE FU1 FU3 TB1 TB2 TB1,TB2, KTK/FNQ-R FU1-FU3 SECONDARY SIDE TOWARD DOOR SECONDARY SIDE LEFT SIDEWALL FRONT VIEW VIEW FROM INSIDE DOOR REMOVED LEGEND — Power Module —...
  • Page 20 a19-1848 NOTE: When replacing the Main Control Board (Item No. 5) the jumper LEGEND marked “J1 HARDWARE ENABLE” must be removed and the jumper 1 — PF750 Series, Precharge Kit marked “J2 SAFETY ENABLE” must be left in place. 2 — PF750 Series, Gate Interface 3 —...
  • Page 21: Appendix A - Wiring Schematics

    APPENDIX A — WIRING SCHEMATICS 19XRV CHILLER CONTROL SCHEMATIC (PIC 3) a19-2378...
  • Page 22 APPENDIX A — WIRING SCHEMATICS (cont) 19XRV CHILLER CONTROL SCHEMATIC (PIC 6)
  • Page 23 APPENDIX A — WIRING SCHEMATICS (cont) 19XRV CHILLER CONTROL SCHEMATIC (PIC 6) (cont)
  • Page 24 APPENDIX A — WIRING SCHEMATICS (cont) 23XRV CHILLER CONTROL SCHEMATIC a23-1731...
  • Page 25 APPENDIX A — WIRING SCHEMATICS (cont) ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical) 19XRV (Typical) SEE METER OPTION DETAIL a19-2327 See Legend on page 26.
  • Page 26 APPENDIX A — WIRING SCHEMATICS (cont) ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical) (cont) 19XRV (Typical) (cont) PIC6 CAT# 20-COMM-H a19-2331 LEGEND — Capacitor — Circuit Breaker — Common COMM — Communication COND — Condenser — Control Relay DPI/SI — Internal Communication Protocols Connections —...
  • Page 27 APPENDIX A — WIRING SCHEMATICS (cont) ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical) (cont) 23XRV (Typical) a19-2328 See Legend on page 28.
  • Page 28 APPENDIX A — WIRING SCHEMATICS (cont) ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical) (cont) 23XRV Typical (cont) a19-2329 LEGEND — Capacitor — Circuit Breaker — Common COMM — Communication COND — Condenser — Control Relay DPI/SI — Internal Communication Protocols Connections —...
  • Page 29 APPENDIX A — WIRING SCHEMATICS (cont) ROCKWELL POWERFLEX 755 WIRING SCHEMATIC (Typical) (cont) 19XRV,23XRV METER OPTION a19-2330...
  • Page 32 © Carrier Corporation 2019 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53190061-01 Printed in U.S.A. Form 19/23-8SS Pg 32 6-19 Replaces: 19/23-7SS...

This manual is also suitable for:

23xrv series

Table of Contents