Data Logging

Data Logging
The energy logger can be started and stopped multiple
times without needing to connect it to a computer.
Starting a Logger
Once a logger has been connected, pressing and
holding the logging button will start it recording. On
screen prompts will confirm the logger has started,
and a logging icon will be shown on the display.
Logging Interval
As supplied the logger is configured to record at a five
minute logging interval. This logging will allow the logger to
record for six weeks when three-phase current and voltage
is being monitored. If less phases are being monitored, the
logger will record for longer.
The logger can be configured to record from a minimum of
once every 30 seconds to a maximum of once every 10 days,
using the supplied Tinytag Explorer software.
Stopping a Logger
Logging can be stopped at any time by pressing
and holding the logging button. On screen prompts
will confirm the logger has been stopped and the
logging icon will disappear.
Multiple Logging Runs
The logger can record multiple logging runs, using the
logging button to start and stop recording sessions as
required.
By default, the logger will keep recording, over-writing the
oldest data when its memory is full. The logger can be set
to stop recording when it fills its memory using the Tinytag
Explorer software.