5

Technical notes

Limitations

5 Technical notes
5.1
18
Building Technologies
CPS Fire Safety
Special Settings on AMS Server with multiple IP addresses
If the AMS server (NICE/RIVER video server) is equipped with network adapter(s)
handling more than one IP address, make sure to apply the following setting:
1. On the AMS server, edit the configuration file ApplicationServer.API.dll.config
2. In the configuration file, set the EventConnectionUsingMachineName flag to true
Limitations
Currently, the support of NICE/RIVER DVR units is subject to the following limitations
(please check latest news with customer support):
Maximum number of connectable DVR units per Server or FEP is 150 (100
recommended for best performance).
Maximum number of AMS Server is 4.
Special types of alarms (e.g. traffic, baggage, intrusion) are all mapped in MM8000
as motion detection alarms.
Data and time synchronisation fails if a registration is in progress on the DVR unit.
Redundant AMS Servers cannot be supported, which means that a NICE/RIVER
DVR can be associated to one AMS Server only.
Only 1 playback per station at the time is possible, even when quad-view is used.