3.8 Synchronizing up to 6 Protection Devices Using 2 Channels

3.8

Synchronizing up to 6 Protection Devices Using 2 Channels

Certain applications, such as line differential protection, require a high-precision second pulse in addition to
the protocols for time synchronization. The Sync-Transceiver can forward both types of time information in
parallel to up to 6 SIPROTEC 4 or SIPROTEC 5 devices using the cascadable Y bus cable 7XV5105-0AAxx.
Table 3-7
Switch
S1/1
S1/2
S1/3
S1/4
[dw_synchron_7SD5x-devices_in_separat-systems, 1, en_US]
Figure 3-7
34
DIP Switch Positions in the Sync-Transceiver
Position
Application-specific (light idle state mode as per the system configuration at the optical-fiber
input R1)
Application-specific (light idle state mode as per the system configuration at the optical-fiber
input R2)
Open (2-channel mode)
Open
Synchronizing Line Differential Protection Devices in Separate Plants
Accessories, Sync Transceiver, Optical/Electrical Converter for Time Synchronization, Manual
C53000-G9050-C168-1, Edition 09.2019