Perkins 1106C Troubleshooting Manual page 33

Table of Contents

Advertisement

KENR6933
Table 21
Minimum
Maximum
0 rpm
3000 rpm
Throttle Lock Increment Speed Ramp
Rate
The "Throttle Lock Increment Speed Ramp Rate"
is the rate of engine acceleration when the PTO
switch is held in the ACCELERATE position. If this
parameter is set to "0", the feature is turned off.
Table 22
Minimum
Maximum
0 rpm/sec
600 rpm/sec
Throttle Lock Engine Set Speed
Increment
The "Throttle Lock Engine Set Speed Increment"
controls the increase in engine speed when the
PTO switch is briefly operated to ACCELERATE or
DECELERATE. If this parameter is set to "0", the
feature is turned off.
Table 23
Minimum
Maximum
0 rpm
200 rpm
Miscellaneous
Monitoring Mode Shutdowns
"Monitoring Mode Shutdowns" controls the shutdown
feature that is associated with the engine monitoring
feature. When this feature is enabled and an event
code with a "-3" suffix is detected, the engine will be
shut down.
Table 24
Value
Disabled
Enabled
Monitoring Mode Derates
"Monitoring Mode Derates" controls the derate that is
associated with the engine monitoring feature. When
this feature is enabled and an event code with a "-2"
is detected, the engine will be derated.
Table 25
Value
Disabled
Enabled
Default
0 rpm
Default
400 rpm/sec
Default
10 rpm
Default
Disabled
Default
Enabled
Limp Home Desired Engine Speed
The "Limp Home Desired Engine Speed" is the
maximum speed of the engine when the engine has
been derated.
Table 26
Minimum
Maximum
700 rpm
1800 rpm
J1939 Continuous Fault Handling
Remote Torque Speed Control Enable
Status
The "Remote Torque Speed Control Enable Status"
parameter determines the way that faults will be
handled by the ECM when the "J1939 Torque Speed
Control (TSC1)" message is used as a speed request
input to the ECM. Programming the "Remote Torque
Speed Control Enable Status" to "Enabled" will cause
the ECM to display a fault code if a valid TSC1
message is not received by the engine ECM within
30 seconds of the engine starting. If the" Remote
Torque Speed Control Enable Status" is programmed
to "Disabled", the engine will display a 247-12 Data
Link malfunction immediately after a loss of a TSC1
message. Program "Remote Torque Speed Control
Enable Status" to "Enabled" if the ECM will always be
receiving a TSC1 message.
Table 27
Value
Disabled
Enabled
Configurable Inputs
Coolant Level Sensor
A coolant level sensor is an optional switch input.
Programming the "Coolant Level Sensor" parameter
to "Enabled" notifies the ECM that a coolant level
sensor input is present on pin J1:38. If this parameter
is programmed to "Enabled" and the coolant level
falls below the measured level, a "E2143-3" event
code will be displayed.
Table 28
Value
Installed
Not Installed
33
Troubleshooting Section
Default
1200 rpm
Default
Disabled
Default
Not Installed