Figure 31. Key "KC" in Lock #3 with the lock pin retracted.
5.
Align the 38 kV SEG&TD with the breaker cell to be tested.
Move and hold the slide handles towards the center of the 38
kV SEG&TD then insert the SEG&TD into the breaker cell to
be tested (see Figure 32). For "Quick Installation Guide" see
Figures 33-35. For detailed "Step-by-Step Installation Guide"
see Appendix B.
It may prove beneficial to have an assistant or use the 38kV VCP-HD
N
otee:
Cradle Assist Kit (style No. 71C2570G01) to help with inserting the 38 kV
SEG&TD into the breaker cell due to the weight of the device and the location
of the slide handles.
Figure 32. Positioning the slide handles for insertion or removal
from the breaker cell.
10
EATON www.eaton.com
38 kV Type VCPW-HD Simple Electrical
Ground & Test Device (SEG&TD) lower
Figure 33. VCPW-HD Racking Screw rotational position when
fully in CONNECT & TEST positions.
Figure 34. VCPW-HD Cell slots for Breake Shoot Bolt Pin inser-
tion for DISCONNECT and TEST position.
6.
Once fully inserted into the breaker cell (Test Position Slot –
Figure 34), release the slide handles and rotate key "KC" to the
"Locked" position. This will extend the locking pin for Lock #3
to lock the slide handles and the SEG&TD within the breaker
cell. At this point, key "KC" remains in Lock #3 until the 38kV
SEG&TD "Racking" operation is complete.
N
otee:
When inserting the 38 kV SEG&TD there are two available positions
(shown in Figure 34): "Disconnect" or "Test" . If in the "Disconnect" posi-
tion as shown in (Figure 35), the 38kV SEG&TD cannot be racked in. Follow
instructions in the description under (Figures 35) and reference (Figure 34)
showing the "TEST" position slot that will permit the 38kV SEG&TD to be
racked in.
Figure 35. VCPW-HD Shoot Bolt Handles must be pulled and
held inward when inserting breaker into the DISCONNECT and
TEST positions. Be sure the handles return to the outward posi-
tion when the breaker is placed in the TEST position or breaker
will not be able to be racked in. Breaker cannot be racked when
in the DISCONNECT position.