Grundfos TPE2 Installation And Operating Instructions Manual page 42

Table of Contents

Advertisement

Measured parameter
Select one of the parameters, such as the parameter
to be measured in the system by the sensor
connected to the actual analog input. See fig. 56.
5
11
1
3
13
DPT
PT
PT
TT
2
4
DPT
DPT
9
LT
Fig. 56
Overview of sensor locations
Sensor function, measured
parameter
Inlet pressure
Diff. press., inlet
"Outlet pressure"
Diff. press.,outlet
Diff. press.,pump
Operating mode
Press. 2, external
Diff. press., ext.
Storage tank level
Feed tank level
Pump flow
Flow, external
Liquid temp.
TPE3, TPE3 D: The temperature
is measured by the built-in sensor.
Temperature 1
Temperature 2
Diff. temp., ext.
Ambient temp.
Other parameter
42
6
14
Q
PT
TT
12
8 16
15
7
Q
DPT DTT
PT
TT
10
LT
Pos.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Not shown
Not shown
Unit
Available measuring units:
Parameter
Possible measuring units
Pressure
bar, m, kPa, psi, ft
Level
m, ft, in
3
Flow rate
m
Liquid temp.
°C, °F
Other parameter
%
Electrical signal
Select signal type:
0.5-3.5 V
0-5 V
0-10 V
0-20 mA
4-20 mA.
Sensor range, minimum value
Set the minimum value of the connected sensor.
Sensor range, maximum value
Set the maximum value of the connected sensor.
Factory setting
See section
34. Factory
settings.
3
/h, l/s, yd
/h, gpm

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tpe3Tpe2 dTpe3 d

Table of Contents