8.5.1 Connection terminals, advanced functional
module, FM 300
The advanced module has these connections:
•
Three analog inputs.
•
One analog output.
•
Two dedicated digital inputs.
•
Two configurable digital inputs or open-collector
outputs.
•
Input and output for Grundfos Digital Sensor.
The input and output are not applicable for TPE2,
TPE2 D pumps. The built-in sensor for TPE3,
TPE3 D pumps is connected to this input.
•
Two Pt100/1000 inputs.
For some pumps, the built-in temperature sensor
is connected to Pt100/1000 input 1 (terminals 17
and 18).
•
Two LiqTec sensor inputs.
•
Two signal relay outputs.
•
GENIbus connection.
See fig. 19.
Digital input 1 is factory-set to be start-stop
input where open circuit results in stop. A
jumper has been factory-fitted between
terminals 2 and 6. Remove the jumper if
digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be
connected to the connection groups
below are separated from each other by
reinforced insulation in their entire
lengths.
•
Inputs and outputs
All inputs and outputs are internally separated
from the mains-conducting parts by reinforced
insulation and galvanically separated from other
circuits.
All control terminals are supplied by protective
extra-low voltage, PELV, thus ensuring protection
against electric shock.
•
Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250
VAC.
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from
other circuits. Therefore, you can connect the
supply voltage or protective extra-low voltage
to the output as desired.
•
Mains supply, terminals N, PE, L or L1, L2, L3,
PE
14
OC
DI
+24 V*
+24 V*
+24 V*
+24 V*/5 V*
OC
GND
+24 V*
+24 V*
+24 V*
+24 V*/5 V*
+
+24 V*
+24 V*
+24 V*/5 V*
*
If you use an external supply source, make sure
that there is a connection to earth.
Fig. 19
Connection terminals, FM 300 (option)
NC
C1
NO
NC
C2
NO
18
GND
11
DI4/OC2
19
Pt100/1000
17
Pt100/1000
12
AO
GND
9
+5 V*
14
AI3
1
DI2
21
LiqTec
20
GND
22
LiqTec
DI
10
DI3/OC1
4
AI1
2
DI1
+
5
+5 V
6
GND
A
GENIbus A
Y
GENIbus Y
B
GENIbus B
3
GND
15
+24 V
8
+24 V
26
+5 V
23
GND
25
GDS TX
24
GDS RX
+5 V*
7
AI2