KaDeck
ceiling cassette
Installation and operating instructions
Keep these instructions in a safe place for future use!
Kampmann.de/installation_manuals
I506 12/19 EN SAP-Nr. 1221711

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KaDeck and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Kampmann KaDeck

  • Page 1 KaDeck ceiling cassette Installation and operating instructions Keep these instructions in a safe place for future use! Kampmann.de/installation_manuals I506 12/19 EN SAP-Nr. 1221711...
  • Page 2: Table Of Contents

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions General ....................About these instructions ............. Explanation of symbols ............Copyright protection ............Customer service ..............Safety ....................Intended use ................. Limits of operation and use ..........
  • Page 3 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.5 Fan setting ................45 6.10.2.6 Time setting ................46 6.10.2.7 Timer programs ..............47 6.10.2.8 Deleting all timer programs and time ........ 50 6.10.2.9 Operating mode changeover – Cooling mode / Heating mode changeover ..........
  • Page 4: General

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions General About these instructions These instructions ensure the safe and efficient handling of this equipment. These instructions form an integral part of the unit and must be kept in the direct vicinity of the unit and available to personnel at all times.
  • Page 5: Copyright Protection

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Other labels The following labels are used in this manual to highlight instructions, results, listings, references and other elements: Label Explanation Step-by-step instructions Results of actions...
  • Page 6: Safety

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Safety This section provides an overview of all important safety aspects to ensure optimum protection of personnel as well as safe and trouble-free operation. Additional order-related safety information is contained in the sections covering the individual phases of the product's life.
  • Page 7 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Water quality pH value 8 – 9 Conductivity S/cm < 700 Oxygen content (0 mg/l < 0.1 Hardness °dH 4 – 8.5 Sulphur ions (S) not measurable...
  • Page 8: Fundamental Dangers

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 2.3. Fundamental dangers The following section lists residual risks that can be generated by the unit even when operated as intended. Observe the following safety instructions and the safety...
  • Page 9: Responsibility Of The Operator

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Responsibility of the operator Duties of the operator The unit is operated in the commercial sector. The operator of the unit is therefore subject to the legal obligations concerning occupational health and safety.
  • Page 10: Personnel Requirements

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Personnel requirements 2.6.1 Qualifications Only permit personnel to carry out work if they can be expected to carry out this work reliably. People with impaired reactions, possibly due to drugs, alcohol or medication, are not permitted to carry out work.
  • Page 11: Technical Data

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Technical data Main dimensions of under-ceiling unit (dry cooling) one- and two-sided discharge (dimensions in mm) Weights Connections, female thread Eurokonus, same end, connections on right...
  • Page 12: Main Dimensions Of Suspended Ceiling Unit (Dry Cooling)

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Main dimensions of suspended ceiling unit (dry cooling) one- and two-sided discharge (dimensions in mm) Weights Connections, female thread Eurokonus, same end, connections on right Unterdeckengerät, einseitig ausblasend Unterdeckengerät, zweiseitig ausblasend...
  • Page 13: Main Dimensions Of Under-Ceiling Unit (Wet Cooling)

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Main dimensions of under-ceiling unit (wet cooling) one- and two-sided discharge (dimensions in mm) Weights Connections, female thread Eurokonus, same end, connections on right Unit design...
  • Page 14: Main Dimensions Of Suspended Ceiling Unit (Wet Cooling)

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Main dimensions of suspended ceiling unit (wet cooling) one- and two-sided discharge (dimensions in mm) Weights Connections, female thread Eurokonus, same end, connections on right Unit design...
  • Page 15: Operating Data

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Operating data Version: one-sided discharge for under-ceiling installation One-sided discharge Dry cooling model Wet cooling model Speed range Maximum Medium Minimum Maximum Medium Minimum Control voltage Air volume V[m³/h]...
  • Page 16 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Version: one-sided discharge for suspended ceiling installation One-sided discharge Dry cooling model Wet cooling model Speed range Maximum Medium Minimum Maximum Medium Minimum Control voltage Air volume V[m³/h]...
  • Page 17: Construction And Function

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Construction and function Overview Connecting frame Ceiling panel Invisible latches Air outlets Air inlet Invisible latches Features...
  • Page 18 KaDeck to the 2-pipe system optimum accessibility suspended ceiling Waterside connection: a dew-point monitor can...
  • Page 19: Brief Description

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Brief description The KaDeck is a decentralised unit for heating, cooling and filtering air, including in hotels, offices and business premises. Thanks to the efficient, extremely quiet fan, the individual comfort temperature is quickly reached. Operating mode Secondary air is drawn into the central part of the ceiling panel. The air is routed first through the air intake grille to...
  • Page 20: Accessories

    LCD multifunctional display, integrated room KaController room temperature sensor, communication interface control unit 196003210021 to Kampmann T-LAN bus system, automatically all models with one-key operation switching LED backlight, press/turn dial with click stop function, individually adjustable basic display, integrated day, night and week program, password-...
  • Page 21 196003232122 without BACnet wall housing, wired ready-for-use, including KaControl operating unit for the central control of Kampmann products via a serial bus communication all models (Modbus); for integration of a maximum of 24 units KaControl SEL panel (Modbus subscribers) (optionally with a maximum of...
  • Page 22: Transport, Packaging And Storage

    The size of the packaging is based on the unit supplied: [mm] [mm] [mm] KaDeck for under-ceiling installation, one-sided discharge 1383 KaDeck for under-ceiling installation, two-sided discharge 1383 KaDeck for suspended ceiling installation, one-sided discharge 1453 KaDeck for suspended ceiling installation, two-sided discharge 1453...
  • Page 23: Transport Inspection

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Transport inspection Check on delivery for completeness and transport damage. Proceed as follows in the event of visible damage: Do not accept delivery or only accept with reservations.
  • Page 24: Storage

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Storage Storing packaging Store packaging under the following conditions: Do not store outdoors. Store in a dry and dust-free place. Do not expose to aggressive media.
  • Page 25: Installation

    (the maximum room height can be significantly lower, depending on the room shape, type of ceiling, use of the room and system temperatures, with under-ceiling units that are also used for heating!) Avoid: Impairing the free circulation of air with lamps, furniture etc. Obstacles to air distribution and air intake. Electronic appliances below the KaDeck.
  • Page 26: Suspending The Unit

    With a rigid plasterboard ceiling, a corresponding cut-out is produced with the adjacent dimensions. Fit the suspension brackets on the KaDeck. Mark the drill positions on the ceiling (one-sided: 490 mm x 1050 mm / two-sided: 620 mm x 105 mm).
  • Page 27: Wet And Dry Cooling Models

    Installation and operating instructions Wet and dry cooling model Distinction A distinction is made between two basic models of KaDeck – dry and wet cooling. Never connect dry cooling units to an on-site water system in which the temperature could fall below the dew point!
  • Page 28: Water Connection With Wet Cooling

    First check whether there is water in the tray or the pipework. Dismantle the tray, as described under section 8.3.3. First fit the flexible hose to the angle valve (including sealing work) and then the angle valve to the KaDeck. Screw the thermostat valve and the return shut-off valve using an appropriate sealant (e.g. NEO Fermit) to the Eurokonus connections on the convector. Now the actuator can be fitted...
  • Page 29 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Tighten the nut and check that the hose clamp is sitting correctly. Attach the condensation pump. " Check whether the plug , the hose , and the air vent are fitted and sufficiently tightened.
  • Page 30 Nein innen dampfdiffusionsdicht isoliert Druckverluste Primärluftstutzen Condensation drain The wet cooling model of the KaDeck includes a built-in KaDecks in der Ausführung feuchte Kühlung beinhalten zur Kondensatabfuhr eine eingebaute Kondensatpumpe mit condensation pump with float switch to drain away any KaDeck in der Ausführung feuchte Kühlung Falls es notwendig wird, das Kondensat höher Schwimmerschalter.
  • Page 31: External Fresh Air Supply

    KaDeck 2-seitiger Luftauslass: 80 m³/h Der Anschluss kann bei allen Varinaten von oben Dazu wird die Anstanzung an der Oberseite des KaDeck 1-sided air discharge: 50 m³/h über einen bauseitigen 100 mm Flansch erfolgen. Gerätes entfernt. KaDeck 2-sided air discharge: 80 m³/h Dazu wird die Anstanzung an der Oberseite des Gerätes entfernt.
  • Page 32: Wiring

    Regulations stipulated by the regional energy supply companies. Only connect the unit to fixed cables. Applications KaDeck units are solely intended for use indoors (e.g. residential and commercial properties, showrooms etc.). They are not suitable for use in humid environments, such as swimming pools or outdoors.
  • Page 33 Modifications to the unit Do not undertake any modifications or upgrades on the KaController or KaDeck without discussing them with the manufacturer as they can impair the safety and operation of the unit. Do not carry out any measures on the unit not described in this manual.
  • Page 34: Overview Of Controls

    3 mm up to a rated voltage of 480 V). No protective measures are indicated in the Kampmann wiring diagrams. These must be provided additionally when installing the system and when connecting the units in accordance with VDE 0100 and the regulations of each of the respective energy supply companies.
  • Page 35: 230 V Electromechanical Model

    The clock thermostat 30456 permits the operation and temperature control of 230 V electromechanical KaDeck units. The room temperature is set by sensor-controlled functional keys. Complete with 10-stage fan speed adjustment in manual and automatic operating mode, including automatic summer/winter changeover and a day or week program.
  • Page 36 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 37: Kacontrol Model

    Installation and operating instructions 6.10 KaControl model The KaControl version provides the option of controlling and networking the KaDeck by means of a control unit supplied separately or on-site building management technology. A number of different settings and configurations are possible using the DIP switches on the PCB and parameters that can be set by the control unit.
  • Page 38: Intended Use

    Installation and operating instructions 6.10.1 Intended use Kampmann KaControllers and KaControl modules are built in line with the state of the art and recognised safety regulations. Nevertheless, their use can result in danger to people or damage to the units or other material property if they are not appropriately installed and operated or correctly and properly used.
  • Page 39: Operation Of The Kacontroller

    Installation and operating instructions 6.10.2 Operation of the KaController The KaController is capable of controlling the wide range of Kampmann systems. KaControllers are equipped with state of the art technology and offer users the option of adapting the air conditioning of buildings to individual needs.
  • Page 40 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions The KaController is operated by the navigator dial and the function keys. The functions that can be called up and set using the navigator dial are identical on both versions (with and without function keys on the side).
  • Page 41: Function Keys, Display Elements

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.1 Function keys, display elements Display with LED background lighting ON/OFF button (depending on setting) – ON / OFF (factory setting) – Eco mode/Day mode TIMER button –...
  • Page 42: Switching Control Off And On

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.2 Switching control off and on When the controller is switched on, the display shows the default view with the current room temperature setpoint and the fan stage set.
  • Page 43: Temperature Adjustment (Absolute Value)

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.3 Temperature adjustment (absolute value) The temperature setpoint is entered from the standard view. To call up the standard view, press ESC or do not touch the KaController for 3 seconds.
  • Page 44: Temperature Setting (Relative Value, Comfort Control Active)

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.4 Temperature setting (relative value, comfort control active) The temperature setpoint is entered from the standard view. To call up the standard view, press ESC or do not touch the KaController for 3 seconds.
  • Page 45: Fan Setting

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.5 Fan setting Press the FAN key (quick access) or use the navigator dial to call up the “Fan setting” selection menu. Calling up the “Fan setting” menu using the navigator dial:...
  • Page 46: Time Setting

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.6 Time setting Press the TIMER key (quick access) or use the navigator dial to call up the “Time setting” selection menu. Calling up the “Time setting” menu using the navigator dial:...
  • Page 47: Timer Programs

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.7 Timer programs The KaController provides the option of programming switching on and off times using a timer program if rooms are only to be air conditioned during certain times of the day.
  • Page 48 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Press the TIMER key twice (quick access) or use the navigator dial to call up the “Timer programs” selection menu. Use the navigator dial to call up the “Timer programs” menu:...
  • Page 49 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Step 4: Set the switch-off time you require by turning the navigator dial. Once the minutes have been set, press the navigator dial ( Step 1) to apply the switching-off time and to call up the timer start screen (action 1).
  • Page 50: Deleting All Timer Programs And Time

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.8 Deleting all timer programs and time Perform the following steps to delete all timer programs and the time: 1. Switch off the KaController by: Pressing the ON/OFF key...
  • Page 51: Heating Mode Changeover

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.10.2.9 Cooling mode / Heating mode changeover Press the MODE key (quick access) or use the navigator dial to call up the “Operating modes” selection menu.
  • Page 52: Alarm Messages

    The alarm messages are displayed according to their priority. In the event of an alarm, note down the alarm message and contact the responsible member of staff (System Administrator or Installer/Service Technician) to fix the fault quickly. KaDeck alarm table Code Alarm Priority Faulty control sensor...
  • Page 53: Kacontroller Installation

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.12 KaController installation Installation/dismantling Electrical wiring Connect the KaController to the nearest KaControl in accordance with the wiring diagram. The maximum bus length between the KaController and the KaControl is 30 m.
  • Page 54: Troubleshooting A11 - A17

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.13 Troubleshooting A11 – A17 Faults in the motor of a slave unit are not shown on the KaController. Only a motor fault in a master unit is shown on the KaController.
  • Page 55 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions A14 Condensation alarm The condensation alarm of a unit is shown on the KaController by the display “A14”. A unit with an active condensation alarm automatically closes all valves.
  • Page 56: Cabling

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.14 Cabling 6.14.1 General information Route all low voltage cables along the shortest route. Ensure that low-voltage and power cables are separated, using metal partitions on cable harnesses.
  • Page 57: External Room Temperature Sensor

    A temperature sensor to measure the air intake temperature or room temperature is factory-installed in all KaDeck with KaControl. The internal sensor in the unit is factory-defined as an internal room temperature sensor and DIP switch no. 6 is set to OFF.
  • Page 58: Addressing - Single-Circuit Controls

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.15 Addressing – Single-circuit controls KaControl units in single-circuit controls with a maximum of 6 units need not be addressed. Define the master unit/slave unit by connecting the KaController.
  • Page 59: Setting Configuration Of Unit By Means Of Dip Switch

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.16 Setting the unit configuration by means of DIP switches Set the configuration of a KaControl unit using the DIP switch on the PCB. Once the DIP switch has been set, all the basic functions of the configuration have been parametrised and the KaControl can be operated immediately.
  • Page 60 Alternatively, cooling/heating changeover can also be performed by an external switch contact. In this case, DIP switch no. 4 has to be set to ON. The KaDeck is designed as a 2-pipe unit and the DIP switch is set to ON. Factory setting: DIP4 = ON DIP switch no.
  • Page 61: Parameter Settings

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.17 Parameter settings Special system requirements can be configured using parameter settings in the Service menu. Special system requirements may include: display: room temperature or setpoint temperature lock operating functions set absolute setpoint temperature or ±...
  • Page 62: Setting The Absolute Setpoint Temperature Or ± 3K

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.17.1 Setting absolute setpoint temperature or ± 3K Parameter P36 It may be necessary in office or hotel applications for the system operator to specify a base setpoint. The user has the option of changing the setpoint temperature by ±...
  • Page 63: On/Off, Eco/Day Functions

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 7.17.2 ON/OFF, Eco/Day function Parameter P38 The ON/OFF key function and the timer programs are specified using parameter P38. Use the ON/OFF button and the timer programs to switch the unit ON and OFF or between Eco and Day mode.
  • Page 64: Function Of Di2

    Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.17.3 DI2 function On the KaDeck, the digital input DI2 is connected to GND via a factory-inserted electrical jumper. The KaDeck is therefore pre-set as a cooling unit.
  • Page 65: Function Of Digital Outputs V1 And V2

    The function of the digital output V2 can be configured using parameters. Digital output V2 KaDeck have been solely developed as 2-pipe units. The output V2 can therefore be parametrised with other functions. The digital output V2 can be configured using parameter P39.
  • Page 66: Function Of Multifunctional Inputs Ai1, Ai2 And Ai3

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.17.5 Function of multifunctional inputs AI1, AI2 and AI3 The function of the multifunctional inputs AI1, AI2 and AI3 can be configured using parameter settings. Function AI1 – Parameter P15 Parameter PI5 is used to set the function of the multifunctional input AI1.
  • Page 67 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Function AI2 – Parameter P16 Parameter PI6 is used to set the function of the multifunctional input AI2. The multifunctional input AI2 can only be set using parameter P16 if DIP switch no.
  • Page 68: Functional Test Of The Connected Assemblies

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.18 Functional testing of connected assemblies The KaController provides the option of checking the function of the external units connected independently of the software application. The function of individual assemblies, such as the EC fan, can be directly activated and checked by means of inputs on the KaController.
  • Page 69: Parameter List For Control Pcb

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.19 Parameter list for control PCB Standard KaDeck Function parameter Min. Max. Unit parameters (Rev. 1.19) P000 Software version P001 Base setpoint for setpoint entry ± 3K °C...
  • Page 70 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Standard KaDeck Function parameter Min. Max. Unit parameters (Rev. 1.19) P044 Function of digital input DI2 P045 Threshold voltage for potentiometer, which switches on unit kOhm...
  • Page 71 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Standard KaDeck Function parameter Min. Max. Unit parameters (Rev. 1.19) P088 Dependence of idronic algorithms Slave 8 P089 Dependence of idronic algorithms Slave 9 P090 Dependence of idronic algorithms Slave 10...
  • Page 72: Kacontroller Parameters

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.20 KaController parameters 6.20.1 General Specific user requirements can be enabled and disabled by means of parameter settings in the KaController, for instance the minimum and maximum setpoint temperature can be set using parameters in the KaController.
  • Page 73: Kacontroller Parameter List

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 6.20.3 KaController parameter list Function Standard Min. Max. Unit Comment t001 Serial address t002 Baud rate 0 = Baud rate 4800 1 = Baud rate 9600...
  • Page 74 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 75 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 76 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 77: Operation And Commissioning

    Check before initial commissioning whether all necessary conditions have been met so that the unit can function safely and properly. Kampmann GmbH can also perform a functional check (optional). For contact details please refer to Chapter 1.4 “Customer service” on page 5.
  • Page 78: Venting The Heat Exchanger

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Check whether the condensation pump is switched on at the relevant water level, the water is draining and the pump switches off again. Check whether the cooling valve is switched off when the maximum liquid level in the condensation tray is exceeded.
  • Page 79: Switching On

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Switching on Switch on the mains voltage. Start up the unit using the control unit connected. Check the fan speeds by switching the stage selector. Check the correct operation of the heating or cooling valves by altering the room temperature setpoint.
  • Page 80: Maintenance Schedule

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Secure against reconnection Switch off the unit. Switch off the energy supply. Position a sign on the isolating switch from the supply network indicating that work is being performed in the hazard area and prohibiting the unit from being switched on.
  • Page 81: Maintenance Work

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Maintenance work Personnel: Caretaker/user Protective equipment: Protective gloves Goggles Lightweight breathing protection The following safety instructions apply to all relevant maintenance work. CAUTION! Risk of injury from sharp metal housing! The inner metal of the casing can have sharp edges.
  • Page 82: Changing Filters

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 8.3.1 Changing filters Switch off unit before opening the intake cover! Open the intake cover until the securing catch snaps into place. Press the securing hook to the inside of the unit and lower the intake cover.
  • Page 83: Cleaning / Visual Inspections

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 8.3.2 Cleaning / Visual inspections Open intake cover, as described in 8.3.1. (optional) The intake cover can also be fully removed to clean it, simply removing the securing bolts in the hinges. After cleaning the cover, as shown in the diagram, re-insert the securing bolts and secure with the securing washer.
  • Page 84: Extended Cleaning Work For The Wet Cooling Model

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 8.3.3 Extended cleaning work for the wet cooling model In addition to the steps described under point 8.3.2, the wet cooling version also needs the condensation tray to be cleaned, and the condensation pump, float switch and drain need to be checked (including the on-site condensation drain).
  • Page 85: Faults

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions Faults The following chapter describes possible causes of faults and the work needed to rectify them. Should faults occur frequently, shorten the maintenance intervals in line with the actual loading on the unit.
  • Page 86: Fault Table

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions Fault table Only permit authorised personnel to rectify operational faults! The table below shows possible faults and the action needed to rectify them: Fault Possible cause...
  • Page 87: Dismantling And Disposal

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 10 Dismantling and Disposal After the unit has come to the end of its service life, it must be dismantled and disposed of in an environmentally friendly manner.
  • Page 88: Disposal

    3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions 10.3 Disposal Recycle dismantled components if no return or disposal agreement has been concluded: Scrap metals. Recycle plastics. Sort and dispose of other components. IMPORTANT NOTE!
  • Page 89: Declaration Of Conformity

    KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions 11 Declaration of Conformity Information requirements for fan coils according to regulation (EU) No 2016/2281 Informationsanforderungen für Fan Coils gemäß Verordnung (EU) Nr. 2016/2281 KaDeck heating and cooling heizen und kühlen...
  • Page 90 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 91 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 92 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 93 KaDeck 3.26 Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 94 3.26 KaDeck Versatile air conditioning for offices and administration buildings Installation and operating instructions...
  • Page 96 Kampmann.eu/KaDeck Kampmann.co.uk/KaDeck Kampmann GmbH Kampmann UK Ltd. Friedrich-Ebert-Str. 128 - 130 Dial House, Govett Avenue 49811 Lingen (Ems) Shepperton, Middlesex, TW17 8AG Germany Great Britain +49 591 7108-660 +44 (0)1932 228592 +49 591 7108-173 +44 (0)1932 228949 export@kampmann.de info@kampmann.co.uk Kampmann.eu...