Siemens RDG100KN Basic Documentation page 77

Room thermostat with knx communications
Hide thumbs Also See for RDG100KN:
Table of Contents

Advertisement

Plant type
2-pipe and
2-pipe fan coil unit with electric heater
electric
– Control sequence: No impact (P01 = any)
heater
– Fan operation: Not disabled (P52 <> 0)
2-pipe and
2-pipe fan coil unit with radiator
radiator
– Control sequence: No impact (P01 = any)
– Fan operation: Not disabled (P52 <> 0)
4-pipe
4-pipe fan coil unit
– Control sequence: Not auto c/o (P01 <> 3)
– Fan operation: Not disabled
Fan coil unit main / secondary
– Control sequence: Auto c/o
– Fan operation: Not disabled
2-stage
2-stage fan coil unit
heating or
– Control sequence: No impact (P01 = any)
cooling
– Fan operation: Not disabled
Siemens
Building Technologies
Application
Configuration
(P52 <> 0)
(P01 = 3)
(P52 <> 0)
(P52 <> 0)
RDG100KN Basic documentation
Supported KNX tools
Application
Configuration
Single stage with electric heater
– Control sequence: No impact (P01 =any)
– Fan operation: Disabled
Single stage with radiator
– Control sequence: No impact (P01 =any)
– Fan operation: Not disabled (P52 <> 0)
Chilled ceiling with radiator
– Control sequence: No impact (P01 =any)
– Fan operation: Disabled
Main / secondary
– Control sequence: Auto c/o
– Fan operation: Disabled
2-stage
– Control sequence: No impact (P01 =any)
– Fan operation: Not disabled
(P52 = 0)
(P52 = 0)
(P01 = 3)
(P52 = 0)
(P52 = 0)
77 / 86