Operation - Siemens RDG100KN Basic Documentation

Room thermostat with knx communications
Hide thumbs Also See for RDG100KN:
Table of Contents

Advertisement

Layout
Button operation
70 / 86
Siemens
Building Technologies
4.3

Operation

See also Operating Instructions B3191 [2] enclosed with the thermostat.
1
3
User action
Normal operation
Press any button
(thermostat in normal operation)
Press left button
Press left button (P01 = 2)
Press left button while "Operating
mode" via bus is Economy or while
operating mode switchover contact is
activated
Keep left button depressed and
turn rotary knob clockwise / counter-
clockwise
Press right button >3 seconds
Press right button for fan coil unit
Press right button if P52 = 0 (fan dis-
abled, e.g. in chilled ceiling applica-
tions)
Turn rotary knob
Press left and right button >3
seconds, release, then press right
button >3 seconds
Press left and right button for 3
seconds, release, press left button for
3 seconds, then turn rotary knob
counterclockwise min. ½ revolution
Press left and right button simultane-
ously for 6 seconds
RDG100KN Basic documentation
Handling
1. Operating mode selector / Esc
2
2. Fan mode selector / Ok
3. Rotary knob to adjust setpoints and
parameters
Effect, description
Actual operating mode and state are
indicated by symbols
Enter operating mode selection;
backlit LCD turns on, all possible mode
symbols turn on, indicator element (arrow)
will appear on the current mode / state
Change operating mode (indicator element
(arrow) changes to the next mode symbol.
After the last press and a timeout of 3
seconds, the newly selected mode is
confirmed, the other elements disappear.
After a timeout of 20 seconds, the LCD
backlight turns off
Toggle between heating and cooling
Activate "Extend Comfort mode"
(for details, see page 16)
Activate timer "Extend presence" / "Extend
absence" and set the time (for details, see
page 16)
Activate / deactivate button lock
Change fan mode
Set thermostat to Protection mode
Adjust the room temperature Comfort
setpoint
Enter parameter setting mode "Service
level"
Enter parameter setting mode "Expert level",
diagnostics and test
Enter (KNX) programming mode
CE1P3191en
22 Jun 2010