Siemens RDG100KN Basic Documentation page 27

Room thermostat with knx communications
Hide thumbs Also See for RDG100KN:
Table of Contents

Advertisement

Application
Output Y1
2-pipe
H/C valve
2-pipe & el heater H/C valve
2-pipe & radiator
H/C valve
4-pipe
Heating valve Cooling valve
4-pipe & el heater Heating valve Cooling valve El heater
2-stage
1st H/C
Note
Dew point monitoring
K NX
R
Fault state
Fault information
Button lock
Siemens
Building Technologies
The "Floor temperature limitation" function influences the outputs listed in the table
below:
Output Y2
Output Y3
El heater
Radiator
2nd H/C
Either floor temperature sensor or external room temperature sensor can be used.
Dew point monitoring is essential to prevent condensation on the chilled ceiling
(cooling with fan disabled, parameter P52). It helps avoid associated damage to
the building.
A dew point sensor with a potential-free contact is connected to multifunctional
input X1, X2 or D1. If there is condensation, the cooling valve is fully closed until no
more condensation is detected, and the cooling output is disabled temporarily.
The condensation symbol " " is displayed during temporary override and the fault
"Condensation in room" will be sent via bus.
The input must be commissioned accordingly (P38, P40, P42).
See section 3.9 "Multifunctional input".
If the "Button lock" function is enabled by parameter P14, the buttons will be locked
or unlocked by pressing the right button for 3 seconds.
If "Auto lock" is configured, the thermostat will automatically lock the buttons 10
seconds after the last adjustment.
RDG100KN Basic documentation
Functions
"Floor temp. limit" function has impact on
Heating
Cooling
(P01 = 0/2/3)
(P01 = 1/2/3)
Y1
N/A
Y2
Y2 *)
Y2
Y2
Y1
N/A
Y3
N/A
Y1, Y2
N/A
*) If P13 = ON
 electric heater in cooling mode
Heat. and cool.
(P01 = 4)
Remark
Only el heater
Only radiator
Y1
Y3
Only el heater
CE1P3191en
22 Jun 2010
27 / 86