3.11.8 Fault function on KNX

If a fault occurs (e.g. digital fault input, dew point, communication configuration,
etc.) then a fault will be sent on the bus.
An RDG thermostat listens on the bus and sends its fault when the fault has the
highest alarm priority. This ensures that the management station does not miss any
alarms.
If alarms occur at the same time, the alarm with the highest priority will be first
displayed and sent on the bus.
Fault transmission is different in LTE mode and S-mode:
S-mode
Fault state
Fault information
(internal
information)
The table below shows the error code and default alarm texts.
Thermostat
Fault
Display
No fault
---
Bus power supply**)
Device address error
Condensation
External fault input X1
External fault input X2
External fault input D1
Clean filter reminder
*)
Default alarm texts are stored in the thermostat's non-volatile memory and can
be adjusted using the ACS700 commissioning tool
**) This error will not be sent on bus (because there is no bus!)
 Priority order is #1...7
 External faults #4...6: If faults are active, the display will show AL1, AL2, AL3,
alternating. On the bus, only the fault with the highest priority will be sent
A supervisor alarm system may command the thermostat to stop sending faults to
the bus via the communication object "Fault transmission" (disable / enable).
This has no impact on the local display of faults.
After a timeout of 48 hours, the sending of faults will automatically be enabled
again.
RDG100KN Basic documentation
Functions
LTE mode
Alarm info (error code + internal information)
Alarm text (default text can be edited with ACS700 tool)
Fault information on bus
Error code
Default fault text
0
No fault
5000
No bus power
bus
supply
6001
>1 id device address
Addr
4930
Condensation in the
room
9001
Fault input 1
AL1
AL2
9002
Fault input 2
AL3
9003
Fault input 3
FIL
3911
Dirty filter
Text
adjustable *)
---
---
57 / 86
CE1P3191en
22 Jun 2010