Technibel KPSW 2 Installation Instructions Manual page 17

Floor or ceiling type terminal units

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 12
4 - connEctIons
GEnEraL
• Remove the side panel so as to facilitate access to the connections.
4.1 - HYDraULIc connEctIon
4.1.1 - GEnEraL
• Water inlet and outlets by 1/" male connections with gas thread.
• For cold water use, a motor-operated valve must be installed, otherwise
there is a risk of condensate if the unit shuts down due to a thermostat
disconnection.
On option: Set of  insulated flexible tubes equipped with a 1/" female
connection with gas thread and a 1/" male connection with gas thread,
installation side.
Two lengths are available: 70600060
4.1.2 - InsULatIon oF pIpEs
• The insulation concerns the water return and inlet pipes.
• Use polyethylene sheathing at least 9 mm thick.
• once connections have been made, check for leaks, install the insulating sleeves supplied
with the unit onto the intake and outlet connections to avoid condensation.
notE: this operation must be done carefully to avoid any risk of condensation.
4.1.3 - pUrGInG tHE aIr HanDLEr's watEr cIrcUIt
• This is done by unscrewing a drain plug located on the exchanger collecting receptacle.
• Access: via the air outlet by using a tool.
4.2 - connEctInG tHE conDEnsatE DIscHarGE pIpE
(For air handlers which can operate in cooling mode)
• Connect the condensate pipe to a discharge pipe.
• Use a flexible tube of internal diameter 18 mm to be fixed on the condensate tube's end piece.
IMportant notE
• Make sure that the slope is correct for proper condensate evacuation.
• Check that condensate drainage is correct and smooth. To do this, use a bottle to pour water into the condensate recovery
tray.
4.3 - ELEctrIcaL connEctIon
4.3.1 - GEnEraLs
• The electrical connection conduits must be fixed.
• Class 1 unit.
• The electrical installation must be carried out in compliance
with the rules in force (especially NFC 15-100
364).
4.3.2 - DEtaIL oF tHE connEctIon
• To have access to the terminal board:
- remove the front suction grille and remove the electrical
box cover (1 screw).
• Prepare the electrical wiring (strip length: 5mm), pass
the cable through the various openings and cable clamps
provided and connect the wires to the terminal strip.
• note: The terminals are of the "cage with spring" type.
Follow the indications below to connect them:
- These terminals take rigid wires.
- A single conductor per securing point.
- Make sure that the wires are correctly connected to the terminal board. Incorrect connection can cause operating problems
as well as overheating which can cause fires.
4.3.3 - powEr sUppLY
• 30V / 1+Earth / 50Hz power supply from a power supply and protection device (not included) in accordance with with the
rules in force especially NFC 15-100 (
• The voltage variation tolerance is ± 10 % during operation.
• Max. protection rating: 6 A.
• Max. current consumption: 0,3 A.
• Section of power cable: 1.5 mm
• Connections are made on the unit's terminal strip (terminals U, N and ground).
:
550 mm,
70600059
: 1 50 mm.
CEI
CEI 364).
.
condensate pipe
water circuit connections
purge screw
terminal board
F
side panel
GB
I
E
D
Insulation
7