Wiring For Communication With Serial Devices - YOKOGAWA UTAdvanced Series User Manual

Communication interface (rs-485, ethernet)
Table of Contents

Advertisement

4.5 Ethernet-Serial Gateway Function
4.5.2

Wiring for Communication with Serial Devices

Parameter
symbol
BPS
PRI
Parameter
symbol
PSL
BPS
PRI
STP
DLN
ADR
4-16
For wiring, see the Operation Guide or User's Manual. A maximum of 31 serial devices
are connectable. Set a communication address (02 to 99) different from each other for
each device.
Note
When Ethernet-serial gateway function is used, do not set the communication address '1' for
the RS-485 communication serial devices connected to the Ethernet-connected UT75A/UT55A/
UT35A/UP55A/UP35A.
 Setting for Devices Working as Ethernet-serial Gateway Function
Set the following communication conditions.
Group
Name
display
Baud rate
E3
Parity
Figures in parentheses "( )" are values to be set when performing communication.
 Setting for Serial Devices Connected to Ethernet-connected UT55A/UT35A/UP55A/
UP35A
Set the following communication conditions for the serial devices connected to the
RS-485 communication line.
Group
Name
display
UT75A/
Protocol
UT55A/
selection
UP55A:
E3, E4
Baud rate
UT52A/
UT32A/
Parity
UP32A/
UM33A:
Stop bit
E1
Data length
UT35A/
Address
UP35A:
E3
Figures in parentheses "( )" are values to be set when performing communication.
 How to Access Serial Devices
See "4.3 Configuration of Network Frame."
Setting range
9600 bps
9600 (4)
19200 bps
19200 (5)
38400 bps
38400 (6)
None
NONE (0)
Even
EVEN (1)
Odd
ODD (2)
Setting range
Modbus (RTU)
MBRTU (8)
9600 bps
9600 (4)
19200 bps
19200 (5)
38400 bps
38400 (6)
None
NONE (0)
Even
EVEN (1)
Odd
ODD (2)
1 bit
1 (1)
8 bits
8 (8)
2 to 99
Menu symbol
Initial value
38400 (6)
ETHR
EVEN (1)
Menu symbol
Initial value
MBRTU (8)
19200 (5)
EVEN (1)
R485
1 (1)
8 (8)
1
IM 05P07A01-01EN