Input Setting (D5101 To D5300) - YOKOGAWA UTAdvanced Series User Manual

Communication interface (rs-485, ethernet)
Table of Contents

Advertisement

Input Setting (D5101 to D5300)

Register
No.
D5101
IN
D5102
UNIT
D5103
DP
RH
D5104
D5105
RL
D5106
SDP
D5107
SH
D5108
SL
D5109
BSL
D5110
RJC
D5111
ERJC
D5112
A.BS
A.FL
D5113
D5114
A.SR
IM 05P07A01-01EN
Description
PV input type
PV input unit
PV input decimal point position
Maximum value of PV input range
Minimum value of PV input range
PV input scale decimal point position
Maximum value of PV input scale
Minimum value of PV input scale
PV input burnout action
PV input reference junction
compensation
PV input external RJC setpoint
PV analog input bias
PV analog input filter
PV analog input square root
extraction
6.4 UT55A/UT52A/UP55A D Registers
Range and meaning of value
0: OFF (Disable)
1: K1 (-270.0 to 1370.0°C / -450.0 to 2500.0 F)
2: K2 (-270.0 to 1000.0°C / -450.0 to 2300.0 F)
3: K3 (-200.0 to 500.0°C / -200.0 to 1000.0 F)
4: J (-200.0 to 1200.0°C / -300.0 to 2300.0 F)
5: T1 (-270.0 to 400.0°C / -450.0 to 750.0 F)
6: T2 (0.0 to 400.0°C / -200.0 to 750.0 F)
7: B (0.0 to 1800.0°C / 32 to 3300 F)
8: S (0.0 to 1700.0°C / 32 to 3100 F)
9: R (0.0 to 1700.0°C / 32 to 3100 F)
10: N (-200.0 to 1300.0°C / -300.0 to 2400.0 F)
11: E (-270.0 to 1000.0°C / -450.0 to 1800.0 F)
12: L (-200.0 to 900.0°C / -300.0 to 1600.0 F)
13: U1 (-200.0 to 400.0°C / -300.0 to 750.0 F)
14: U2 (0.0 to 400.0°C / -200.0 to 1000.0 F)
15: W (0.0 to 2300.0°C / 32 to 4200 F)
16: PL2 (0.0 to 1390.0°C / 32.0 to 2500.0 F)
17: P2040 (0.0 to 1900.0°C / 32 to 3400 F)
18: WRE (0.0 to 2000.0°C / 32 to 3600 F)
30: JPT1 (-200.0 to 500.0°C / -300.0 to 1000.0 F)
31: JPT2 (-150.00 to 150.00°C / -200.0 to 300.0 F)
35: PT1 (-200.0 to 850.0°C / -300.0 to 1560.0 F)
36: PT2 (-200.0 to 500.0°C / -300.0 to 1000.0 F)
37: PT3 (-150.00 to 150.00°C / -200.0 to 300.0 F)
40: 0.4-2V (0.400 to 2.000 V)
41: 1-5V (1.000 to 5.000 V)
42: 4-20 (4.00 to 20.00 mA)
50: 0-2V (0.000 to 2.000 V)
51: 0-10V (0.00 to 10.00 V)
52: 0-20 (0.00 to 20.00 mA)
55: -1020 (-10.00 to 20.00 mV)
56: 0-100 (0.0 to 100.0 mV)
*W: W-5% Re/W-26% Re(Hoskins Mfg. Co.), ASTM E988
WRE: W97Re3-W75Re25
0, 2, 3, 4: - (No unit)
1: C (Degree Celsius)
5: F (Degree Fahrenheit)
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
Depends on the input type.
- For temperature input -
Set the temperature range that is actually controlled. (RL<RH)
- For voltage / current input -
Set the range of a voltage / current signal that is applied.
The scale across which the voltage / current signal is actually
controlled should be set using the maximum value of input
scale (SH) and minimum value of input scale (SL).
(Input is always 0% when RL = RH.)
Same as D5103
-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000
0: OFF (Disable)
1: UP (Upscale)
2: DOWN (Downscale)
0: OFF (RJC OFF)
1: ON (RJC ON)
-10.0 to 60.0°C
-100.0 to 100.0% of PV input range span (EUS)
0: OFF
1 to 120 s
0: OFF (No square root extraction.)
1: Compute the square root. (The slope equals "1.")
2: Compute the square root. (The slope equals "0.")
6
6-85

Advertisement

Table of Contents
loading