Setting the Input Range
Setting the Temperature Measurement Channel, the Input Range, and the Tag
IM 04L21B01-02EN
Configure the FX so that it measures temperature on measurement channel 1 and flow
rate on measurement channel 2.
Type T
Channel 1
thermocouple
0.0 to 200.0°C
Setup Item
Description
Channel
Use channel 1.
Tag
TI-001
Sensor
Type T thermocouple
Input range
0.0 to 200.0°C
(1) Input Range
Press MENU (switch to the setting mode).
Select the Menu tab > Meas channel > Range, Alarm.
Setting Procedure
1.
Display the operation mode screen.
2.
Press MENU once to display the setting menu.
3.
Press the down arrow key twice to select Meas channel.
4.
Press the right arrow key once.
Setting the Functions and Operations
FX
Number in the Figure
1
2
3
4
1
4
3
Select the Range, Alarm.
19