Troubleshooting (OP: Schedule Timer)

5.

Troubleshooting (OP: Schedule Timer)

" UE "
5.1
Malfunction of Transmission Between Centralized

Controller and Indoor Unit

UE
Remote
Controller
Display
Applicable
Schedule timer
Models
All models of indoor units
Method of
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
238
Malfunction of transmission between central remote controller and indoor unit
Disconnection of connector for setting master controller (or individual/combined switching
connector)
Defect of schedule timer PC board
Defect of indoor unit PC board
Si39-504