Jc" Outdoor Unit: Malfunction Of Low Pressure Sensor; Malfunction Of Low Pressure Sensor - Daikin VRV II RXYQ5MATL Service Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

Si39-504
3.31 " JC " Outdoor Unit:
JC
Remote
Controller
Display
Applicable
RXYQ5MA~48MA
Models
Method of
Malfunction is detected from pressure detected by low pressure sensor.
Malfunction
Detection
Malfunction
When the suction pipe pressure sensor is short circuit or open circuit.
Decision
Conditions
Supposed
Causes
Troubleshooting
∗1: Voltage measurement point
∗2: Refer to "Pressure Sensor, Pressure / Voltage Characteristics" table on P301.
Troubleshooting

Malfunction of Low Pressure Sensor

Defect of low pressure sensor system
Connection of high pressure sensor with wrong connection.
Defect of outdoor unit PC board.
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
The low
pressure sensor is
connected to X45A (blue)
of outdoor unit PC
board (A1P).
YES
The
relationship
between the ∗1
VH and low pressure is
normal (see ∗2) when voltage
is measured between X45A pins
(2) and (3) of outdoor unit
PC board (A1P)
(see ∗1).
NO
Troubleshooting by Indication on the Remote Controller
NO
YES
Connect low pressure sensor
property and restart system.
Replace outdoor unit PC board
(A1P).
Replace the low pressure sensor.
(V2808)
205