Daikin VRV II RXYQ5MATL Service Manual page 204

R-410a heat pump 60hz
Table of Contents

Advertisement

Si39-504
∗1 Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
×: No continuity
Troubleshooting
Pin No.
1. White
: Continuity
Troubleshooting by Indication on the Remote Controller
2. Yellow
3. Orange
×
Approx.
300Ω
×
4. Blue
5. Red
×
Approx.
150Ω
×
Approx.
300Ω
×
Approx.
150Ω
×
6. Brown
×
Approx.
150Ω
×
Approx.
150Ω
×