Digital Inputs; Analogue Inputs - Carel pCO5 Technical Leaflet

Table of Contents

Advertisement

Available languages

Available languages

The versions with valve driver, with or without Ultracap module, have the same number, type and confi guration of I/Os as the
Medium version.

Digital inputs

type
maximum number voltage inputs optically-
isolated
maximum number inputs free contact not
optically-isolated
Classifi cation of measurement circuits (IEC EN
61010-1)
Voltage-free digital input current
(B4, B5, B9, B10)
Digital input current with 24 Vac voltage signal 5 mA
Digital input current with 230 Vac voltage signal 5 mA
WARNINGS:
- IDH digital inputs 230 Vac 50/60 Hz (10/-15%) protected by a single 500 mAT fuse;
- the two 230/24 Vac inputs at J8 and J12 have the same common and so both will be either
24 Vac/Vdc or 230 Vac. There is double insulation between the two inputs and the rest of the controller;
- the external contact connected to the digital inputs must have a minimum current of 5 mA;
- for DC digital inputs (Vdc), either the + or the – can be connected to the common (IDC1).
Note:
separate as much as possible the probe signal and digital input cables from the cables to inductive loads and power cables,
to avoid possible electromagnetic disturbance.
Fast digital input specifi cations (B4 and B5 voltage-free contact)
When confi gured as fast digital inputs, B4 and B5 can measure a signal with a maximum frequency of 2 KHz and a resolution of ±1
Hz. This is possible as the BIOS provides the application program two pairs of variables that count the zero crossing of the input
signal and the corresponding frequency in Hz.

Analogue inputs

analogue conversion
type
maximum number
time constant for each input
precision
class. of measurement circuits
(IEC EN 61010-1)
input impedance
WARNING:
the 21 Vdc available at terminal +Vdc (J2) can be used to power any active probes; the maximum current is 150 mA,
protected against short-circuits. To power the 0 to 5 Vdc ratiometric probes, use the +5V
Only use these voltages to power the active probes connected to pCO
+0500040RU - 1.2 - 07.06.2011
lantaclimate.ru
ID1 to ID18 optically-isolated (voltage contact), B4, B5, B9, B10 non optically-
isolated (free contact)
8: SMALL; 14: MEDIUM & EXTRALARGE ; 18: LARGE. As per combinations shown
below:
SMALL
MEDIUM/
EXTRALARGE
LARGE
2: SMALL, MEDIUM & EXTRALARGE (B4 and B5);
4: LARGE (B4, B5, B9, B10)
Category 1 (J5, J7, J20) 24 Vac/Vdc - Category 3 (J8, J19) 230 Vac
5 mA
10-bit A/D converter embedded in CPU
universal: (inputs B1, B2, B3, B6, B7, B8) CAREL NTC temperature sensor (-50T90 °C; R/T 10 k at 25 °C),
NTC HT 0T150 °C, voltage: 0 to 1 Vdc, 0 to 5 V ratiometric or 0 to 10 Vdc, current: 0 to 20 mA or 4
to 20 mA, selectable via software. Input resistance for 0 to 20 mA= 100
passive: (inputs B4, B5, B9, B10) CAREL NTC temp. sensor (see universal),
PT1000 (-100T200 °C; R/T 1000  at 0°C) or volt.-free digital input (5 mA), selected via software;
5: SMALL; 8: MEDIUM & EXTRALARGE; 10: LARGE
0,5 s
± 0.3 % of full scale
Category 1
NTC
10 kΩ
4-20 mA
100 Ω
0-1 V
100 kΩ
0-5 V
20 kΩ
0-10 V
12,7 kΩ
PT1000
10 kΩ
no. 24 Vac opto inputs
no. 24 Vac/Vdc or 230 Vac opto
50/60 Hz o 24 Vdc
8
12
14
(Imax: 60 mA) available at terminal J24.
REF
5
.
7
ENG
total
inputs (50/60 Hz)
inputs
none
8
2
14
4
18