4.2 Checking the IGBTs, static test

Always carry out the static test of the IGBTs after each repair.
Before beginning the test:
1. Switch off the mains supply, and wait until the capacitors have
discharged.
2. Remove the supply cable.
3. Remove the motor cable.
4. Set the multimeter to diode test.
The test shown here is actually a test of the freewheel diode of
the IGBT component. If the freewheel diode is okay, it is assumed
that the IGBT component is so too.
Terminals in enclosures A2 and A3 (shown with
mains supply cable connected).
Enclosures A5 and B3 have similar terminals.
+DC
-DC
+DC
-DC
DC+
DC-
DC+
DC-
Measurements
Step 1
Step 2
DC+
-
+
DC-
L1
+
-
L2
+
-
L3
+
-
Indication
OL
OL
+ = positive test pin
- = negative test pin
Measurements
Step 1
Step 2
DC+
-
+
DC-
L1
+
-
L2
+
-
L3
+
-
Indication
OL
OL
+ = positive test pin
- = negative test pin
Measurements
Step 1
Step 2
DC+
+
-
DC-
U
-
+
V
-
+
W
-
+
Indication
OL
0.4
+ = positive test pin
- = negative test pin
Measurements
Step 1
Step 2
DC+
+
-
DC-
U
-
+
V
-
+
W
-
+
Indication
OL
0.4
+ = positive test pin
- = negative test pin
Step 3
Step 4
+
-
-
+
-
+
-
+
0.4
OL
Step 3
Step 4
+
-
-
+
-
+
-
+
0.4
OL
Step 3
Step 4
-
+
+
-
+
-
+
-
OL
0.4
Step 3
Step 4
-
+
+
-
+
-
+
-
OL
0.4