Technical Specifications - Bosch FLM-420-RLV1-E Installation Manual

Relay interface modules low voltage

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 12
12
en
NOTICE!
Installation must only be performed by authorized and specialized personnel!
The connected device must have a minimum activation time of 20 ms.
CAUTION!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
DANGER!
Live components and stripped cable! Risk of injury from electric shock.
The system must be current-free during connection work.
Functional description
The FLM-420-RLV1 Relay Interface Module Low Voltage has a change-over contact relay to provide a potential free
output contact.
The FLM-420-RLV1-E type in-built can be flush mounted in standard device boxes in accordance with EN 60670;
alternatively, it can be installed in the devices (see Figure 6 to Figure 7, Page 7).
Address setting
Address setting is carried out using the 8 DIP switches and a suitable pointed object (see Figure 1 to Figure 4, Page 4
and the following tables).
Address (A)
Operating mode
0
Loop/stub in LSN improved version mode with automatic addressing
1 — 254
Loop/stub/T-tap in LSN improved version mode with manual addressing
255 = CL
Loop/stub in LSN classic mode (address range: max. 127)
Connection
Terminals
LSN: a1- | b1+ | a2- | b2+
LSN-POWER: 0 V | 0 V | +24 V | +24 V
LSN-SHIELD
REL1: COM | NO | NC
Figure 5 Page 7 shows the relay connected as
-
NO contact: continuous line
-
NC contact: dotted line.

Technical specifications

Relay
LSN input voltage
Max. current consumption from LSN
Max. switched current and voltage (resistive load)
Min. switched current and voltage
Minimum activation time of the connected device
Permissible wire diameter
Permissible operating temperature / storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Classes of equipment as per IEC 60950
Housing material and color
Dimensions
F.01U.013.004 | 6.0 | 2010.06
Function
LSN in / LSN out
LSN power supply (support points to loop through)
Cable shielding (if present)
Change-over relay (COM/NO contact/NC contact)
1 low voltage relay (NO/COM/NC)
15 to 33 V DC
1,75 mA
1 A / 30 V DC
0.01 mA/10 mV DC
> 20 ms
2
0.6 to 2.0 mm
-20 °C to +55 °C / -25 °C to +80 °C
<96%, non-condensing
IP 30
Class III equipment
ABS + PC blend, signal white (RAL 9003)
approx. 50 mm x 22 mm (Ø x H)
Bosch Sicherheitssysteme GmbH
FLM-420-RLV1-E