4.1 Nameplate

The CUE can be identified by means of the nameplate.
An example is shown below.
T/C: CUE202P1M2T5E20H1BXCXXXSXXXXAXBXCXXXXDX
S/N: 123456G234
Prod. no: 12345678
1.5 kW (400V)
IN: 3x380-500 V 50/60Hz 3.7A
OUT: 3x0-Vin 0-100Hz 4.1 A 2.8 kVA
CHASSIS/IP20 Tamb. 45C/122F
IIIIIIIIIIIBAR CODEIIIIIIIIIII
Listed 76X1 E134261 Ind. Contr. Eq.
See manual for prefuse
CAUTION:
SEE MANUAL / VOIR MANUEL
WARNING:
STORED CHARGE DO NOT TOUCH UNTIL
4 MIN AFTER DISCONNECTION
CHARGE RESIDUELLE, ATTENDRE
4 MIN APRES DECONNEXION
Fig. 1
Example of nameplate
Text
Description
CUE (product name)
T/C:
202P1M2... (internal code)
Prod. no:
Product number: 12345678
Serial number: 123456G234
S/N:
The last three digits indicate the production date:
23 is the week, and 4 is the year 2004.
1.5 kW
Typical shaft power on the motor
Supply voltage, frequency and maximum input
IN:
current
Motor voltage, frequency and maximum output
OUT:
current. The maximum output frequency usually
depends on the pump type.
CHASSIS/
Enclosure class
IP20
Tamb.
Maximum ambient temperature

4.2 Packaging label

The CUE can also be identified by means of the label on the
packaging.

5. Mechanical installation

The individual CUE cabinet sizes are characterised by their
enclosures. The table in section 16.1 shows the relationship of
enclosure class and enclosure type.

5.1 Reception and storage

Check on receipt that the packaging is intact, and the unit is
complete. In case of damage during transport, contact the
transport company to complain.
Note that the CUE is delivered in a packaging which is not
suitable for outdoor storage.

5.2 Transportation and unpacking

The CUE must only be unpacked at the installation site to prevent
damage during the transport to the site.
The packaging contains accessory bag(s), documentation and
the unit itself. See fig. 2.
MADE IN DENMARK
Accessory
bag(s)
Fig. 2

5.3 Space requirements and air circulation

CUE units can be mounted side by side, but as a sufficient air
circulation is required for cooling these requirements must be
met:
Sufficient free space above and below the CUE.
See table below.
Ambient temperature up to 122 °F.
Hang the CUE directly on the wall, or fit it with a back plate.
See fig. 3.
Fig. 3
Required free space above and below the CUE
Enclosure
A2, A3, A5
B1, B2, B3, B4, C1, C3
C2, C4
For information about enclosure, see table in section 16.1.
Documentation
CUE packaging
CUE hung directly on the wall or fitted with a back
plate
Space [in]
3.9
7.9
8.9
7