Connecting The Signal Terminals - Grundfos CUE Series Installation And Operating Instructions Manual

0.75 - 125 hp
Table of Contents

Advertisement

Available languages

Available languages

6.3 Connecting the signal terminals

As a precaution, signal cables must be separated
from other groups by reinforced insulation in
Caution
their entire lengths.
If no external on/off switch is connected, short-
Note
circuit terminals 18 and 20 using a short wire.
Connect the signal cables according to the guidelines for good
practice to ensure EMC-correct installation. See section
6.6 EMC-correct installation.
Use screened signal cables with a conductor gauge size of
min. 22 AWG and max. 16 AWG.
Use a 3-conductor screened bus cable in new systems.
6.3.1 Wiring diagram, signal terminals
0/4-20 mA
0-10 V
0-10 V
1 K
Fig. 21 Wiring diagram, signal terminals
0/4-20 mA
Terminals
53 and 54:
See section
6.3.5
Terminal Type
Function
12
+24 V out
Supply to sensor
13
+24 V out
Additional supply
18
DI 1
Digital input, start/stop
19
DI 2
Digital input, programmable
20
GND
Ground for digital inputs
32
DI 3
Digital input, programmable
33
DI 4
Digital input, programmable
39
GND
Ground for analog output
42
AO 1
Analog output, 0-20 mA
50
+10 V out
Supply to potentiometer
53
AI 1
External setpoint, 0-10 V/0/4-20 mA
54
AI 2
Sensor input, sensor 1, 0/4-20 mA
55
GND
Ground for analog inputs
61
RS-485 GND Y GENIbus, GND
68
RS-485 A
GENIbus, signal A (+)
69
RS-485 B
GENIbus, signal B (-)
Terminals 27, 29 and 37 are not used.
Note
The RS-485 screen must be connected to ground.
6.3.2 Minimum connection, signal terminals
Operation is only possible when the terminals 18 and 20 are
connected, for instance by means of an external on/off switch or
a short wire.
Fig. 22 Required minimum connection, signal terminals
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents