Table 14 RTC103 N-module, LXV411.99.10111, 2-channels (continued)
Module
Name
1-fold analog input
KL3011
1-fold analog input
KL3011
1-fold analog input
KL3011
Bus end terminal
KL9010
Table 15 RTC103 N-module with O
Module
Name
8-fold digital output KL2408
1-fold analog input
KL3011
1-fold analog input
KL3011
Bus end terminal
KL9010
14 English
Terminal Signal
1(+) 2(-)
0/4 to 20 mA 1
1(+) 2(-)
0/4 to 20 mA 2
1(+) 2(-)
0/4 to 20 mA 2
step control, LXV411.99.11101,1-channel
2
Terminal Signal
1
+24 V/0 V
5
+24 V/0 V
2
+24 V/0 V
6
+24 V/0 V
3
+24 V/0 V
7
+24 V/0 V
4
+24 V/0 V
8
+24 V/0 V
1(+) 2(-)
0/4 to 20 mA 1
1(+) 2(-)
0/4 to 20 mA 1
Channel Function
Flow rate internal recirculation or return
sludge lane 1
Flow rate aeration lane 2
Flow rate internal recirculation or return
sludge lane 2
Bus termination
Channel Function
1
Input Signals OK (24 V), Input signal
defective (0 V)
1
Aeration step 1 ON/OFF
1
Aeration step 2 ON/OFF
1
Aeration step 3 ON/OFF
1
Aeration step 4 ON/OFF
1
Aeration step 5 ON/OFF
1
Aeration step 6 ON/OFF
1
RTC operating (24 V), RTC defective (0 V)
Flow rate aeration lane
Flow rate internal recirculation or return
sludge
Bus termination