8.1
PUSH BUTTONS
The two push buttons located just above the LEDs can be used to adjust the output voltage
when the output is enabled. These buttons are labelled V▲ and V▼. Short presses for a
fraction of a second adjust the output voltage at the output voltage setting resolution. If the
button is held down, the rate of change increases to around 1V/s after 10s. If both buttons
are pressed together, the button adjust is cleared to zero. The PMBus can read the button
adjust value and also clear the value. The PMBus can also be used to enable or disable the
buttons. Note that it may be necessary to adjust the settings of DCOK and OVP using the
PMBus in order not to encounter these when adjusting with the push buttons over a wide
voltage range.
8.2
FRONT PANEL INDICATORS
The two front panel indicators together indicate the status of the power module.
Document Number: BLUESTREAK-MAN Rev. 6
Green LED (top)
LED
Condition
Status
ON
DCOK is TRUE
FLASHING
DCOK is FALSE - unit inhibited
OFF
DCOK is FALSE - unit not inhibited
Red LED (bottom)
LED
Condition
Possible causes
Status
ON
DC output OFF
Temperature above/below allowed limits.
OVP.
Overcurrent or Short Circuit (DCOK goes FALSE).
Processor Failure. (Green LED OFF).
FLASHING
DC output ON
Fans below expected speed.
(warning)
Temperature high/low.
Output current close to maximum.
Output on but DCOK FALSE.
AC input voltage outside range.
OFF
DC output ON
All posible conditions for the LEDs are shown opposite.