Danfoss ICAD 600A Installation Manual page 2

Advertisement

Programming the ICAD
Valve size setup (mandatory)
When powering up the ICAD, A1 will flash in the display
; 01
Hold down
for
2 seconds to enter
programming mode
0
Press
or
to select ICM size or CVE.
Press
NOTE !
If media temperature is lower than -30 °C (-22 °F) it is mandatory to set parameter i30 an i31.
See separate document attached in ICAD box: document number AN285243155312
Changing analogue input signal (optional)
; 01
Hold down
for
2 seconds to enter
programming mode
; 03
Hold down
for
2 seconds to exit
programming mode
For further functions,
programming possibilities
24 Volt DC
and factory settings;
ONLY
please see ICAD instruction.
2 | AN213086423355en-000501
; 10
Press
and
Press
go to parameter 10.
you reach 11 (password).
Press
Press
1: ICM 20 with ICAD 600A
6: ICM 65 with ICAD 1200A
2: ICM 25 with ICAD 600A
7: ICM 100 with ICAD 1200A
3: ICM 32 with ICAD 600A
8: ICM 125 with ICAD 1200A
4: ICM 40 with ICAD 1200A
9: ICM 150 with ICAD 1200A
5: ICM 50 with ICAD 1200A
10: CVE pilot with ICAD 1200A
Valve label ID:
ICM 20
ICM 25-65
; 03
Press
until you
Press
reach parameter 03.
to select analogue
input signal
Press
A3
If A3 alarm occurs
the analogue input
signal is out of range
Note:
If the keypad is not operated within
20 seconds; time out will automatically
exit programming mode.
11
until
Press
you reach parameter 26
Press
ICM/CVE & ICAD
ICM 100-150
is now calibrating
2
or
Factory reset of ICAD
Disconnect power 
Press down
and
simultaneously while
reconnecting power 
Release
and
Note:
If factory reset has been performed the
ICAD will start flashing A1 in the display.
Decrease
value
; 26
until
; 26
Hold down
2 seconds to exit
programming mode
1: 0 – 20 mA
2: 4 – 20 mA*
3: 0 – 10 V
4: 2 – 10 V
* default factory setting
Press
© Danfoss | DCS (ms) | 2020.01
Edit /
Increase
Enter
value
4
CA
for
5
; 03

Advertisement

loading

This manual is also suitable for:

Icad 1200a