Adjustment Elements - Siemens FS720 Quick Reference For Components / Pin Assignment

Fire detection system
Table of Contents

Advertisement

EVAC-NL operating unit FTO2007-N1 [NL]
18.4

Adjustment elements

88
Building Technologies
Fire Safety & Security Products
The EVAC-NL indicator is configured with the switch S20.
Setting for one or first EVAC-NL
Switch S20
1
2
3
4
S0
S1
S2
Master
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
X
X
X
ON
Blank fields = Switch in 'OFF' position
X = Switch position has no impact
* If working with one single EVAC-NL indicator (10 zones) and if working with the
first EVAC-NL indicator, S20/4 (Master) must always be set to ON. If used in the
EVAC-NL mimic display driver, the S20/5 (Syn) switch must also be ON.
Each address can be assigned only once per station.
The factory setting is always made for the application in question.
Setting for the second and/or any subsequent EVAC-NL indicator
Switch S20
1
2
3
4
S0
S1
S2
Master
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
X
X
X
OFF
Blank fields = Switch in 'OFF' position
X = Switch position has no impact
* = 2 EVAC-NL indicators must not be operated on the same address (per station).
On the second or any subsequent indicator, the address must always be set 1
higher (slave). If used in the EVAC-NL mimic display driver, the S20/5 (Syn) switch
must also be ON.
Each address can be assigned only once per station.
The factory setting is always made for the application in question.
Meaning
5
6
Syn
(Empt
y)
OFF
Device address 1 *
OFF
Device address 2
OFF
Device address 3
OFF
Device address 4
OFF
Device address 5
ON
Mimic display outputs are actuated and
polled (LED, keys and key switch)
Meaning
5
6
Syn
(Empt
y)
OFF
Device address 1
OFF
Device address 2 *
OFF
Device address 3
OFF
Device address 4
OFF
Device address 5
ON
Mimic display outputs are actuated and
polled (LED, keys and key switch)
A6V10210410_a_en_--
18.05.2009

Advertisement

Table of Contents
loading

Table of Contents