Pin Assignments - Siemens FS720 Quick Reference For Components / Pin Assignment

Fire detection system
Table of Contents

Advertisement

Element
LEDs
Fuses
Adjustment elements
9.2

Pin assignments

9.2.1
X1 supply
Building Technologies
Fire Safety & Security Products
Des.
Function
H1
Power Down Ready
H201
C-NET module 2 indication
H401
Monitoring supply output 1 (fuse F401)
H402
Monitoring supply output 2 (fuse F402)
H501
Monitoring alarm output (fuse F501)
H601
Monitoring fault output (fuse F601)
H100-
Indications of programmable inputs and outputs
H115
F400
Horn output (1 A/T); Schurter OMT 125
F401
Supply output 1 (1 A/T); Schurter OMT 125
F402
Supply output 2 (1 A/T); Schurter OMT 125
F501
Monitored alarm output (1 A/T); Schurter OMT 125
F601
Monitored fault output (1 A/T); Schurter OMT 125
S100
Switchover of the LED indicators for the inputs and outputs
Inputs and outputs which are not used do not require termination.
C-NET detector lines which are not used must not be terminated.
PIN
Designation
1
#BATT
2
#CONV
3
#MAINS
4
COMMON
5
3SRC+
6
3SRC–
7
VSYS+
8
VSYS+
9
VSYS–
10
VSYS–
Admissible cable cross-section: 0.2 ... 2.5 mm²
Periphery board (2 loops) FCI2002-A1
Description
Message input from the power supply: Battery fault
Message input from the power supply: Converter fault
Message input from the power supply: Mains failure
Ground
Supply input for third supply source (+) [FR]
Supply input for third supply source (-) [FR]
Supply input from the power supply (+)
Supply input from the power supply (+)
Supply input from the power supply (–)
Supply input from the power supply (–)
45
A6V10210410_a_en_--
18.05.2009

Advertisement

Table of Contents
loading

Table of Contents