Siemens FS720 Quick Reference For Components / Pin Assignment page 49

Fire detection system
Table of Contents

Advertisement

9.2.5
X9 configurable inputs/outputs 5 ... 8 and supply output 2
9.2.6
X11 detector line loop 1
Building Technologies
Fire Safety & Security Products
PIN
Designation
6
GND_02
5
VSYS_02
4
I/O8
3
I/O7
2
I/O6
1
I/O5
Admissible cable cross-section: 0.2 ... 1.5 mm²
GND_02
-
VSYS_02
F402
+
I/O8
I/O7
I/O6
I/O5
All inputs/outputs can be connected as follows:
1
Configured as output
2
Configured as input
PIN
Designation
4
LOOP1_2–
3
LOOP1_2+
2
LOOP1_1–
1
LOOP1_1+
Admissible cable cross-section: 0.2 ... 1.5 mm²
X11
LOOP1_2-
-
LOOP1_2+
+
LOOP1_1-
-
LOOP1_1+
+
Comment
One loop or two stubs can be connected.
Periphery board (2 loops) FCI2002-A1
Description
Supply output 2 (–)
Supply output 2 (+)
Configurable input/output 8
Configurable input/output 7
Configurable input/output 6
Configurable input/output 5
X9
6
5
4
2
3
1
2
1
Description
Loop 1 / stub 2 (–)
Loop 1 / stub 2 (+)
Loop 1 / stub 1 (–)
Loop 1 / stub 1 (+)
4
3
2
1
49