Indications - Siemens FS720 Quick Reference For Components / Pin Assignment

Fire detection system
Table of Contents

Advertisement

Periphery board (1-loop) FCI2001-A1
8.3

Indications

LED
Colour
Function
H1
Red
Power Down Ready
H401
Yellow
Supply output 1 (F401)
H501
Yellow
Monitored alarm output (F501)
H601
Yellow
Monitored fault output (F601)
LED
Colour
Function
H102
Yellow
FUE_FAU_1
H103
Yellow
FUE_FAU_2
H104
Yellow
FUE_AL_1
H105
Yellow
FUE_AL_2
H106
Yellow
HORN_1
42
Building Technologies
Fire Safety & Security Products
Indications of supply and system
Indication of outputs
Condition Meaning
Off
Normal operation
On
Control panel may be disconnected from the
mains.
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged
Condition
Meaning
Off
Relay activated (default)
On
Relay not activated
Off
Active (default)
Slow
Open line
Fast
Short-circuit
On
Passive
Off
Relay not activated (default)
On
Relay activated
Off
Passive (default)
Slow
Open line
Fast
Short-circuit
On
Active
Off
Passive (default)
Slow
Open line
Fast
Short-circuit
On
Active
A6V10210410_a_en_--