Indications - Siemens FS720 Quick Reference For Components / Pin Assignment

Fire detection system
Table of Contents

Advertisement

Periphery board (2 loops) FCI2002-A1
9.2.7
X12 detector line loop 2
9.3

Indications

LED
Colour
Function
H1
Red
Power Down Ready
H401
Yellow
Supply output 1 (F401)
H402
Yellow
Supply output 2 (F402)
H501
Yellow
Monitored alarm output (F501)
H601
Yellow
Monitored fault output (F601)
50
Building Technologies
Fire Safety & Security Products
PIN
Designation
4
LOOP2_2–
3
LOOP2_2+
2
LOOP2_1–
1
LOOP2_1+
Admissible cable cross-section: 0.2 ... 1.5 mm²
X12
LOOP2_2-
-
LOOP2_2+
+
-
LOOP2_1-
LOOP2_1+
+
Comment
One loop or two stubs can be connected.
Indications of supply and system
Description
Loop 2 / stub 4 (–)
Loop 2 / stub 4 (+)
Loop 2 / stub 3 (–)
Loop 2 / stub 3 (+)
4
3
2
1
Condition Meaning
Off
Normal operation
On
Control panel may be disconnected from the
mains.
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged
Off
Fuse ok
On
Fuse damaged
A6V10210410_a_en_--
18.05.2009

Advertisement

Table of Contents
loading

Table of Contents